Technical data • Individual components
Chapter 2
Technical data
Power Panel 500 user's manual V1.40
115
3.4.5 5PP5IF.FCAN-00
3.4.5.1 General information
The 5PP5IF.FCAN-00 interface board has one CAN bus master interface and 512 kB SRAM.
•
1x CAN bus master interface
•
512 kB SRAM
•
Compatible with the PP500, APC511 and APC511
This interface board can only be operated with Automation Runtime.
3.4.5.2 Order data
Model number
Short description
Figure
Interface boards
5PP5IF.FCAN-00
CAN interface card - 1 CAN master
Required accessories
Terminal blocks
0TB1208.3100
Connector, 8-pin cage clamp, 1 mm², protected against vibration
by the screw flange
Table 69: 5PP5IF.FCAN-00 - Order data
3.4.5.3 Technical data
Product ID
5PP5IF.FCAN-00
General information
B&R ID code
0xB4DA
Diagnostics
Module status
Yes, using status LED
Data transfer
Yes, using status LED
Terminating resistor
Yes, using status LED
Certification
CE
Yes
cULus
Yes
GOST-R
Yes
GL
Yes
1)
Controller
SRAM
Value
512 kB
Battery-backed
Yes
Remanent variables in power failure mode
256 kB (e.g. for Automation Runtime, see AS help system)
2)
Interfaces
CAN
Quantity
1
Design
8-pin male connector
Transfer rate
Max. 500 kbit/s
Terminating resistor
Type
Can be enabled or disabled using a sliding switch
Default setting
Disabled
Electrical characteristics
Power consumption
3 W
Environmental conditions
Temperature
Operation
0 to 55°C
Storage
-20 to 60°C
Transport
-20 to 60°C
Relative humidity
Operation
5 to 90%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Table 70: 5PP5IF.FCAN-00 - Technical data
1)
Yes, although applies only if all components installed within the complete system have this certification.
2)
With optimized access using write combining