Technical data • Individual components
Secti
on 2
Te
chn
ica
l da
ta
185
Automation PC 620 with 945GME N270 CPU board User's Manual V 1.10
Bus length and cable type
The type of cable used depends largely on the required bus length and the number of nodes.
The bus length is mainly determined by the bit rate. In accordance with CiA (CAN in Automation)
the maximum bus length is 1000 meters.
The following bus lengths are permitted with a maximum oscillator tolerance of 0.121%:
The material used for the cable should preferably have all or most of the following properties in
order to reach an optimal transfer rate.
Distance [m]
Transfer rate [kBit/s]
≤
1000
Typ. 50
≤
200
Typ. 250
≤
60
Typ. 500
Table 88: Bus length and transfer rate - CAN
CAN cable
Property
Signal lines
Cable cross section
Wire insulation
Conductor resistance
Stranding
Shield
2 x 0.25 mm² (24AWG/19), tinned Cu wire
PE
≤
82
Ω
/ km
Wires stranded in pairs
Paired shield with aluminum foil
Grounding line
Cable cross section
Wire insulation
Conductor resistance
1 x 0.34 mm² (22AWG/19), tinned Cu wire
PE
≤
59
Ω
/ km
Outer sheathing
Item
Characteristics
Entire shielding
PUR mixture
Halogen free
From tinned cu wires
Table 89: CAN cable requirements
Содержание 5PC600.SE00-00
Страница 2: ...2 Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10...
Страница 4: ...4 Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10...
Страница 6: ...6 Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10...
Страница 38: ...38 General information Typical topologies Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10...
Страница 202: ...202 Technical data Individual components Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10...
Страница 568: ...568 Appendix A Glossary Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10...