X20 system modules • X20 interface module communication • X20IF1061
1792
X20 system User's Manual 3.10
4.23.8.3 Technical data
Product ID
X20IF1061
Short description
Communication module
PROFIBUS DP V0/V1 master
General information
B&R ID code
0x1F22
Status indicators
Module status, bus status
Diagnostics
Module status
Yes, using status LED and software
Bus status
Yes, using status LED and software
Power consumption
1.4 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
PLC - IF1
Yes
Certification
CE
Yes
cULus
Yes
cCSAus HazLoc Class 1 Division 2
Yes
ATEX Zone 2
Yes
KC
Yes
GOST-R
Yes
Interfaces
IF1 interface
Fieldbus
PROFIBUS DP V0/V1 master
Design
9-pin female DSUB connector
Max. distance
1200 m
Transfer rate
Max. 12 Mbit/s
Terminating resistors
External T-connector (0G1000.00-090)
Controller
EC1
Memory
8 MB SDRAM
Cyclic data
Input data
3.5 kB
Output data
3.5 kB
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Slot
In X20 CPU
Table 566: X20IF1061 - Technical data