494
Software • Upgrade information
Power Panel 300/400 User's Manual V 2.30
•
The system must be rebooted after a successful upgrade.
3.4 User boot logo upgrade disk
A software tool for updating, backing up, or deleting the user boot logo can be downloaded
directly from the service portal of the B&R homepage (
).
Figure 315: aPCI firmware upgrade start menu
Item
Menu item
Description
1
Update FPGA firmware automatically
The firmware for both aPCI slots is automatically updated (default after 5 seconds).
Information:
According to the inserted modules, the aPCI FPGA firmware files are searched
for automatically.
2
Update FPGA firmware of aPCI slot 1
Only firmware from aPCI slot 1 is updated.
Information:
If no aPCI module is present, the aPCI FPGA firmware file must be renamed
"apci1.pci" (for aPCI slot 1) before updating.
3
Update FPGA firmware of aPCI slot 2
Only firmware from aPCI slot 2 is updated.
Information:
If no aPCI module is present, the aPCI FPGA firmware file must be renamed
"apci2.pci" (for aPCI slot 2) before updating.
4
Save FPGA firmware of both aPCI slots
Firmware for both aPCI slots are automatically saved.
Information:
It's necessary to have up to 640 KB of free space on the disk.
5
Exit
Returns to the shell (MS-DOS).
Table 179: aPCI firmware upgrade menu description
Information:
If you do not press a button within 5 seconds, then step 1 "Update FPGA firmware
automatically" is automatically carried out and the Power Panel is automatically
updated.
Microsoft Windows Startup Menu
===================================
1. Update FPGA firmware automatically
2. Update FPGA firmware of aPCI slot 1
3.
4. Save FPGA firmware of both aPCI slots
5. Exit
Enter a choice:_
Update FPGA firmware of aPCI slot 2
Содержание Power Panel 300
Страница 2: ...2 Power Panel 300 400 User s Manual V 2 30 ...
Страница 4: ...4 Power Panel 300 400 User s Manual V 2 30 ...
Страница 6: ...6 Power Panel 300 400 User s Manual V 2 30 ...
Страница 20: ...20 Power Panel 300 400 User s Manual V 2 30 Table of contents ...
Страница 428: ...428 Commissioning User tips for increasing the display lifespan Power Panel 300 400 User s Manual V 2 30 ...
Страница 536: ...536 Standards and certifications International certifications Power Panel 300 400 User s Manual V 2 30 ...
Страница 608: ...Model number index 2 Power Panel 300 400 User s Manual V 2 30 ...
Страница 612: ...Index 4 Power Panel 300 400 User s Manual V 2 30 ...