Standards and certifications • Climate conditions
92
Power Panel 65 User's manual V2.21
5.5.6 Free fall (packaged)
Test carried out in accor-
dance with
EN 60068-2-32
Limits in ac-
cordance with
EN 61131-2
Limits in ac-
cordance with
EN 60721-3-2
class 2M1
Limits in ac-
cordance with
EN 60721-3-2
class 2M2
Limits in ac-
cordance with
EN 60721-3-2
class 2M3
Limits in ac-
cordance with
B&R
Devices with de-
livery packaging
each with 5 fall tests
Devices packaged
Devices packaged
Devices packaged
Devices packaged
Weight
Height
Weight
Height
Weight
Height
Weight
Height
Weight
Height
<10 kg
1.0 m
<20 kg
0.25 m
<20 kg
1.2 m
<20 kg
1.5 m
<40 kg
1 m
10 to 40 kg
0.5 m
20 to
100 kg
0.25 m
20 to
100 kg
1.0 m
20 to
100 kg
1.2 m
-
-
>40 kg
0.25 m
>100 kg
0.1 m
>100 kg
0.25 m
>100 kg
0.5 m
-
-
Devices with prod-
uct packaging each
with 5 fall tests
Weight
Height
<10 kg
0.3 m
10 to 40 kg
0.3 m
Free fall
>40 kg
0.25 m
5.6 Climate conditions
Temperature and humidity
Test carried out in accordance with
Limits in accordance with
Worst case operation
UL 508
UL 508: Industrial control equipment
EN 61131-2: Programmable logic controllers
Dry heat
EN 60068-2-2
EN 61131-2: Programmable logic controllers
Cold
EN 60068-2-1
EN 61131-2: Programmable logic controllers
Large temperature fluctuations
EN 60068-2-14
EN 61131-2: Programmable logic controllers
Temperature fluctuations in operation
EN 60068-2-14
EN 61131-2: Programmable logic controllers
Humid heat, cyclic
EN 60068-2-30
EN 61131-2: Programmable logic controllers
Constant humid heat (storage)
EN 60068-2-3
EN 61131-2: Programmable logic controllers
Sprayed water (from the front)
NEMA 250 type 4X
UL 508 - NEMA 250 4X: Degrees of pro-
tection provided by enclosures (IP code)
5.6.1 Worst case operation
Test carried out
according to UL 508
Limits in accordance with
UL 508
Limits in accordance with
EN 61131-2
Worst case during operation. Operation of the device
with the max. ambient temperature specified in the
data sheet at the max. specified load
3 hours at max. ambient temperature (min. 40°C)
duration approx. 5 hours
3 hours at max. ambient temperature (min. 40°C)
duration approx. 5 hours
5.6.2 Dry heat
Test carried out in accor-
dance with
EN 60068-2-2
Limits in accordance with
EN 61131-2
Dry heat
16 hours at 70°C for 1 cycle, then 1 hour acclimatization and function testing,
duration approx. 17 hours
5.6.3 Dry cold
Test carried out in accor-
dance with
EN 60068-2-1
Limits in accordance with
EN 61131-2
Dry cold
16 hours at -40°C for 1 cycle, then 1 hour acclimatization and function testing,
duration approx. 17 hours
5.6.4 Large temperature fluctuations
Test carried out in accor-
dance with
EN 60068-2-14
Limits in accordance with
EN 61131-2
Large temperature fluctuations
3 hours at -40°C and 3 hours at 70°C for 2 cycles, then 2 hours acclimatization and function testing,
duration approx. 14 hours