TECHNICAL SPECIFICATIONS
MODEL
TBG 260 LX ME
TBG 360 LX ME
Type-approval PIN
CE-0085BS0067
CE-0085BS0067
Maximum natural gas heat power
kW
2700
3600
Minimum natural gas heat power
kW
450
500
¹) natural gas emissions
mg/kWh
Class 3
Class 3
Operation
Electronic modulation
Electronic modulation
50 Hz natural gas transformer
26 kV 40 mA - 230 V
26 kV 40 mA - 230 V
Methane maximum flow rate
Stm³/h
286
381
Methane minimum flow rate
Stm³/h
48
53
Maximum natural gas pressure
hPa (mbar)
360
500
Minimum natural gas pressure
hPa (mbar)
40
107
Maximum propane thermal power
kW
2700
3600
Minimum propane thermal power
kW
450
640
Propane maximum flow rate
Stm³/h
110
147
Propane minimum flow rate
Stm³/h
18
75
Maximum propane pressure
hPa (mbar)
360
500
Minimum propane pressure
hPa (mbar)
70
73
²)propane emissions
mg/kWh
Class 3
Class 3
50hz fan motor
kW
5.5
7.5
50Hz three-phase electrical data
3L - 400V - 10.2A - 6.14kW 3L 400V - 13.7A -8.36kW
50Hz single-phase electrical data
1N - 230V - 0.44A -
0.101kW
1N 230V - 0,44A -
0.101kW
Protection rating
IP40
IP40
Flame detection
IONISATION PROBE
IONISATION PROBE
Control box
BT 320
BT 320
Air flow rate regulation
ELECTRONIC CAM
ELECTRONIC CAM
Operating ambient air temperature
°C
-15 ÷ +40
-15 ÷ +40
Sound pressure**
dBA
89
82
Sound power***
dBA
-
95
Weight with packaging
kg
110
117.3
Weight without packaging
kg
89
96.2
Calorific power below reference conditions 15° C, 1013 hPa (mbar):
Natural gas: Hi = 9,45 kWh/Stm³ = 34,02 MJ/Stm³
Propane: Hi = 24,44 kWh/Stm³ = 88,00 MJ/Stm³
For different types of gases and pressure values, contact our sales departments.
Minimum gas pressure, depending on the type of gas train used for obtaining max. flow rate with null pressure in the combustion chamber.
** The acoustic pressure measured with burner operating at maximum rated thermal output refers to the manufacturer's laboratory environment
conditions and cannot be compared to measurements carried out in different locations. Measurement accuracy σ = +/- 1.5 dB(A).
*** Acoustic pressure was obtained characterizing the manufacturer's laboratory with a sample source; this measurement has a class 2
accuracy (engineering class) with a standard deviation of 1.5 dB(A).
STANDARD ACCESSORIES
MODEL
TBG 260 LX ME
TBG 360 LX ME
Burner connection flange
2
2
Burner coupling flange gasket
1
1
Stud bolts
No. 4 M 12
N° 4 M 12 + N° 4 M16
Hexagon nuts
No. 4 M 12
N° 4 M 12 + N° 4 M16
Flat washers
No. 4 Ø 12
N° 4 Ø 12 + N° 4 Ø 16
7 / 34
0006081328_202202
ENGLISH
Содержание 17530020
Страница 2: ......
Страница 32: ...SCHEMI ELETTRICI TBG 80 360LX ME TBG 80 360 ME 30 34 0006081328_202202 ITALIANO...
Страница 33: ...TBG 80 360LX ME TBG 80 360 ME 31 34 0006081328_202202 ITALIANO...
Страница 34: ...TBG 80 360LX ME TBG 80 360 ME I1 I2 BA I4 I3 32 34 0006081328_202202 ITALIANO...
Страница 36: ...34 34 0006081328_202202 ITALIANO...
Страница 66: ...WIRING DIAGRAMS TBG 80 360LX ME TBG 80 360 ME 30 34 0006081328_202202 ENGLISH...
Страница 67: ...TBG 80 360LX ME TBG 80 360 ME 31 34 0006081328_202202 ENGLISH...
Страница 68: ...TBG 80 360LX ME TBG 80 360 ME I1 I2 BA I4 I3 32 34 0006081328_202202 ENGLISH...
Страница 70: ...34 34 0006081328_202202 ENGLISH...
Страница 71: ......