7.1
Counter function
With the counter function, up to 65536 (16 bits) objects
can be detected by the sensor and evaluated with the help
of the preset value and process data.
The counter state
CountValue
can be read from Register
0x00B7. The counter function is parameterized using the
Switch Counter Settings
parameter in Register 0x00B6.
Use
Limit
to specify a preselected value at the beginning.
After the sensor turns on, the counter begins with counter
state 0 and increments by 1 with each object detection.
When the preset value is reached, the counter output
(process data bit
Count limit
/
Speed ok
) is set.
The counter function can be used in STATIC, AUTO or
SPEED mode. The absolute counter state is output in Byte
0 and Byte 1 of the process data. When the mode is
changed it is automatically reset to 0. In SIO mode Pin 4 or
Pin 2 can be configured as a counter output using the
Pin
Function Selection
parameter. Alternatively Pin 2 can be
configured as
Counter Reset
.
To ignore brief counter pulses,
Debounce Time
can be
used to add a debounce function. The counter only recog-
nizes objects which were detected for longer than the
debounce time.
Counter function/frequency monitor see
7.1.1 Counter Mode STATIC (manual reset)
In STATIC Mode the counter state is continually
incremented with each new object detection. As soon as
the counter state reaches the preselected value, the
Count
limit
/
Speed ok
bit in the process data is set and the
counter continues to increment. The counter state and
counter output can be reset in the process data using the
system command
Counter Reset
or setting the
Counter
Reset
bit.
To perform a reset in SIO mode, Pin 2 must be configured
as an input (parameter 0x00BC). A High signal on the
Reset input resets the counter output. The rising edge is
always used. When there is a continuous Reset signal, the
counter value and counter output are reset only once.
7
IO-Link interface: Additional functions
Fig. 7-1:
Count pulses
RESET
Count Value
Counter output
on
off
Switch Counter Limit
Preselect counter with Reset command
A debounce time (parameter 0x00BA) between
0…65535 ms can be assigned to the Reset input.
7.1.2 Counter Mode AUTO (automatic Reset)
After the preselected value has been reached, the counter
starts counting at counter value 1 with the next detection
of an object and the counter output is reset automatically.
A manual reset is always possible. The configuration of Pin
2 is not changed in Counter Mode AUTO.
Fig. 7-2:
Count pulses
Count Value
Counter output
on
off
Switch Counter Limit
Preselect counter with automatic reset
7.1.3 Frequency monitor
In SPEED Mode, the frequency monitor is activated.
The frequency monitor monitors the system for over- and
under-frequency. For both cases, you can configure a
turn-on and turn-off value using
UpperLimitHigh
/
Low
and
LowerLimitHigh
/
Low
in Register 0x00B6. The minimum
distance between the turn-on and turn-off value is 10 % of
the turn-on value.
As long as the measured frequency remains within the
parameterized expected range, the
SCS: Count limit
/
Speed ok
bit in the process data and Register 0x00B7 is
set. If the measured frequency exceeds the
UpperLimit-
High
switching threshold, the
Speed too high
bit is set. If
the measured frequency falls below the
LowerLimitLow
switching threshold, the bit
Speed Too Low
is set.