www.balluff.com
11
english
5.1
Starting up the system
DANGER
Uncontrolled system movement
When starting up, if the position measuring system is part
of a closed loop system whose parameters have not yet
been set, the system may perform uncontrolled
movements. This could result in personal injury and
equipment damage.
►
Persons must keep away from the system's
hazardous zones.
►
Startup must be performed only by trained technical
personnel.
►
Observe the safety instructions of the equipment or
system manufacturer.
1.
Check connections for tightness and correct polarity.
Replace damaged connections.
2.
Turn on the system.
3.
Check measured values and adjustable parameters
and readjust the transducer, if necessary.
Check for the correct values at the null point
and end point, especially after replacing the
transducer or after repair by the manufacturer.
5.2
Operating notes
– Check the function of the position measuring system
and all associated components on a regular basis.
– Take the position measuring system out of operation
whenever there is a malfunction.
– Secure the system against unauthorized use.
5
Startup
BTL7-V50T-M _ _ _ _ -P-C003
Micropulse Transducer in a Profile Housing
Содержание BTL7-V50T-M-P-C003 Series
Страница 1: ...BTL7 V50T M_ _ _ _ P C003 Betriebsanleitung deutsch...
Страница 2: ...www balluff com...
Страница 20: ...BTL7 V50T M_ _ _ _ P C003 User s Guide english...
Страница 21: ...www balluff com...
Страница 39: ...BTL7 V50T M_ _ _ _ P C003 Manual de instrucciones espa ol...
Страница 40: ...www balluff com...
Страница 58: ...BTL7 V50T M_ _ _ _ P C003 Notice d utilisation fran ais...
Страница 59: ...www balluff com...
Страница 77: ...BTL7 V50T M_ _ _ _ P C003 Manuale d uso Italiano...
Страница 78: ...www balluff com...