www.balluff.com
35
english
5
Configuring with Simatic Step7 V13 (TIA) (continued)
5.3
Example program
A function module can illustrate access from a program. In
line 4 the position value is copied from the peripheral
memory using pointer access. Here the variable
Position_01 was created in the standard variable table as
DInt with address %ID168. The address is 4 bytes over the
I-address previously assigned to the standard telegram 81.
In line 15 the error value 16#7FFFFFFF is checked for.
In addition to this evaluation the other
diagnostics mechanisms available in the PLC
should be used to detect any errors and place
the machine in a safe state when a fault
condition arises.
The remainder of the program example is simple variable
operations which do not need further explanation here.
Fig. 5.4: Example program (FB3)