Balluff BNI PNT-502-102-Z015 Скачать руководство пользователя страница 1

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

BNI PNT-502-102-Z015 

IP67 Module  

User´s Guide 

 

Содержание BNI PNT-502-102-Z015

Страница 1: ...BNI PNT 502 102 Z015 IP67 Module User s Guide...

Страница 2: ...Grounding 7 PROFINET interface 8 I O port 8 IO Link port 8 Port 8 4 Technical data 9 4 1 Dimensions 9 4 2 Mechanical data 9 4 3 Operating conditions 9 4 4 Electrical data 9 4 5 PROFINET 10 4 6 Functio...

Страница 3: ...tartup 25 6 6 Main menu 25 6 7 Factory Reset 26 6 8 Module Info 26 7 Webserver 27 7 1 General 27 7 2 Navigation Info 28 7 3 Login Logout 29 7 4 Home dialog 30 7 5 Ports dialog 32 No appropriate IODD u...

Страница 4: ...ce 44 Specifier 44 Direction 44 8 6 Channel Error Type 45 9 Configuration of IO Link devices 46 General 46 Function block 46 Reading 46 Writing 46 10 Appendix 47 10 1 Scope of delivery 47 10 2 Order n...

Страница 5: ...Step 2 3 Syntax Numbers Decimal numbers are shown without additional information e g 123 hexadecimal numbers are shown with the additional indicator hex e g 00hex or the prefix 0x e g 0x00 Cross refer...

Страница 6: ...oid by Unauthorized tampering Improper use Use installation or handling contrary to the instructions provided in this operating manual Obligations of the Operating Company The device is a piece of equ...

Страница 7: ...502 102 Z015 1 Port 3 2 Port 2 3 Port 1 4 Pin Port LEDs 5 Port 0 6 Power IN 7 Label 8 PROFINET port 1 9 Grounding connection 10 PROFINET port 2 11 Display 12 Power OUT 13 Status LEDs 14 Port 4 15 Port...

Страница 8: ...nsor bus and actuator Total current 9 A The total current of all modules must not exceed 9A even in the case of series connection of the actuator supply Note Interpretation of leads for power supply o...

Страница 9: ...6 A 2 Input output 2A 3 GND 4 Input output 2A 5 FE Note For the digital sensor inputs refer to guideline on inputs EN 61131 2 Type 2 Note Each output receives a maximum current of 2 0 A The total cur...

Страница 10: ...ate Supply voltage 7 8 5 pin connector female Input ports output ports M12 A coded 8x female Dimensions W x H x D in mm 68 x 224 x 37 9 Type of installation Screw installation with 2 securing holes Gr...

Страница 11: ...status LED Display Function US Green Input voltage OK Red flashing Input voltage low 18 V UA Green Output voltage OK Red flashing Output voltage low 18 V Red No output voltage present 11V SF off No e...

Страница 12: ...hort circuit at output at pin 2 4 against pin 3 Red No high signal at diagnostic input IO Link port Status Function Green IO Link connection active Green flashing No IO Link connection or wrong IO Lin...

Страница 13: ...k modules the corresponding data modules are assigned to a slot Integration of the module The device can be found by searching in the catalog and inserted in the Profinet section by drag drop The BNIP...

Страница 14: ...higher the configuration of pin 4 as IO Link port is not necessary anymore The port is automatically configured to IO Link when an IO Link process data module is used in the hardware configuration Th...

Страница 15: ...nk module that corresponds to the process data length of the IO Link device must be selected in the catalog and dragged to the appropriate slot by means of drag drop The process data length required b...

Страница 16: ...lluff com 15 5 Integration IO Link configuration Double click on the IO Link module to change the IO Link parameters of the respective port pins A description of the individual modules is provided in...

Страница 17: ...com 16 5 Integration Device name Profinet address Double click on the module in the Profinet line to view the communication parameters of the module The device name and the Profinet address IP are con...

Страница 18: ...start the tool for assigning the module a device name Assigning device name Select the desired name and use Assign name to assign the marked device that you found The device name must be the same as t...

Страница 19: ...uld be a problem in one of the following areas Device relationship not established Scan the network via Target system Ethernet Ethernet user Search and check whether the device is signaling under the...

Страница 20: ...to the output of the module Optical diagnostics and diagnostics in configured diagnostics modules are not affected This function is valid only for channels pins that are configured as outputs As input...

Страница 21: ...wn pin 4 pin 2 Depicts a short circuit between a set output to ground at the respective port pin Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Port 7 Port 6 Port 5 Port 4 Port 3 Port 2 Port 1 Port 0...

Страница 22: ...rt 1 Port 0 Peripheral error socket Feedback indicating the port at which an error occurred Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Port 7 Port 6 Port 5 Port 4 Port 3 Port 2 Port 1 Port 0 Shor...

Страница 23: ...ta The visible data window for the input data can now be adjusted via an IO Link module with appropriate process data length Validation No validation Validation deactivated every device will be accept...

Страница 24: ...nly the download is enabled the master always starts a download of the parameter data In this case the download is likewise independent of the upload flag of the IO Link device If no data is stored in...

Страница 25: ...isplay 2 Arrow Key 3 Octett Cursor 4 Address type cursor 5 Set Key 6 LEDs Arrow Key This button is used to go through the entries of a menu and is a short time keypress The display shows the default s...

Страница 26: ...rt time keypress on Set Key Step in a menu with short time keypress on Arrow Key Actual state Change over S Condition short time keypress on Set Key S Condition long time keypress on Set Key min 3 sec...

Страница 27: ...confirmed the device performes a restart Note A factory reset can be performed only after a power reset without an attached network cable Module Info 6 8 Go through the Module Info menu with short tim...

Страница 28: ...ure that the module has been correctly integrated into your network In addition the IP subnet of the BNI module must be accessible from the PC on which the browser is running Please use Internet Explo...

Страница 29: ...the upper area of the window which allows you to switch between the various dialogs of the web interface To do this click on the corresponding icon When the Info tab is selected the following overview...

Страница 30: ...T XXX XXX XXXX BNIPNT BNI EIP XXX XXX XXXX BNIEIP BNI ECT XXX XXX XXXX BNIECT The password cannot be changed After successfully logging in the dialogs are shown as follows Use the Logout button to log...

Страница 31: ...ion is also shown about the current process data and the status of the module via the corresponding LEDs After selecting LED Legend a Help dialog appears which explains the meaning of the LEDs If an I...

Страница 32: ...Balluff Network Interface ProfiNet www balluff com 31 7 Webserver PNT EIP...

Страница 33: ...o appropriate IODD uploaded It is possible to read and write the configuration parameters of the IO Link device via the Parameters option The parameter indexes and subindexes of the IO Link device are...

Страница 34: ...for Process Data and Parameters is not displayed but rather an expanded dialog Information from the IODD of the device is used so that the data can be better understood Thus in the following screensh...

Страница 35: ...nt modes These modes can be set using an IO Link parameter The parameter values and associated texts are stored in the IODD This means Operation Mode can be read out and displayed Read and Read All bu...

Страница 36: ...at i e with a restricted name length Since IODD files are generally published with a long file name these must be renamed and given a shorter naming scheme on the PC before uploading to the fieldbus m...

Страница 37: ...The configuration page enables configuration of the module You can change both the module information texts and the port configuration The Set Ports action is not permanently stored in the device and...

Страница 38: ...e Configuration and permanently stored in the device The Reboot button reboots the device as if the power to the module had been turned off and on again Clicking on Factory Reset deletes the configura...

Страница 39: ...upper table see screenshot below contains important information for all service inquiries Note If you have a detailed question about a specific situation send us a screenshot of this Web site or print...

Страница 40: ...ting the module from the outside The system may require troubleshooting Event Informational Notice The fieldbus module has detected an important normal operating event and reports it These may include...

Страница 41: ...ed into 3 blocks Block Header Alarm Specifier Channel Properties Byte Value Meaning Block 0 00 Block Type Block Header 1 02 2 00 Block Length 3 1E 4 01 Block Version High 5 00 Block Version Low 6 00 A...

Страница 42: ...ype of alarm is provided here Possible values Meaning 0x0001 Diagnostics API 4 bytes default is 0 Possible values Meaning 0x00000000 Default value Slot 2 bytes of data that describe which slot of the...

Страница 43: ...es Meaning 0x00 No diagnosis related to manufacturer is pending 0x01 Diagnosis related to channel is pending Submodules Diagnostic State Bit 13 Possible values Meaning 0x00 No further diagnosis of sub...

Страница 44: ...ort 2 pin 4 0x0003 Port 3 pin 4 0x0004 Port 4 pin 4 0x0005 Port 5 pin 4 0x0006 Port 6 pin 4 0x0007 Port 7 pin 4 0x000A Port 0 pin 2 0x000B Port 1 pin 2 0x000C Port 2 pin 2 0x000D Port 3 pin 2 0x000E P...

Страница 45: ...6 32 bit 0x07 64 bit 0x08 0xFF Reserved Accumulative Bit 8 not used always 0 Maintenance Bit 9 10 Possible values Meaning Bit 9 Bit 10 0x00 0x00 Diagnostics Specifier Bit 11 12 Possible values Meaning...

Страница 46: ...rcuit 0x0002 Undervoltage 0x0003 Overvoltage 0x0004 Overload 0x0005 Temperature limit exceeded 0x0006 Cable break 0x0007 Upper threshold exceeded 0x0008 Lower threshold undershot 0x0009 Error 0x001A E...

Страница 47: ...r Port number Reserved 2 65098 FI_Index IO Link header is following IO Link header 1 0 255 Task 2 write 3 read 2 0 3276 7 65535 IO Link index Port function 1 0 255 IO Link subindex Data range 232 Rang...

Страница 48: ...BNI PNT 502 102 Z015 Balluff network interface ProfiNet Functions 502 IP 67 IO Link master module 4 IO Link ports Versions 102 Display version 2 port switch rotated Mechanical version Z015 Die cast zi...

Страница 49: ...www balluff com 48 Notes...

Страница 50: ...www balluff com 49 www balluff com Balluff GmbH Schurwaldstrasse 9 73765 Neuhausen a d F Germany Tel 49 7158 173 0 Fax 49 7158 5010 balluff balluff de No 895700 726 E 09 124983 Edition I17 Replaces Ed...