IO-Link Sensor-Hub
BNI IOL-709-
… / BNI IOL-710-…
www.balluff.com
8
4
IO-Link Interface
Input:
Input-Signal at Port and Pin
Switch Point:
The switch point bits show a switch point
overrun. The switch point can be configured
by parameter ( see 0.0 -
Analogue value:
VV: actual voltage value between
0 and 1056 (1Bit = 0.01V)
CV: actual current value between
0 and 2150 (1Bit = 0.01mA)
Error:
•
Error 1
•
Error 2
•
Error 3
Overcurrent/short circuit on sensor supply
Measurement range overflow
Measurement range undercut (only CV)
4.3
Process data
outputs
There are no outputs at BNI IOL-710-... and BNI IOL-709-... modules.
4.4
Parameter data/
On-request data
DPP
SPDU
Parameter
Data
width
Access
Index
Index
Sub-
index
Id
e
n
tif
ic
a
tion
D
a
ta
07
hex
Vendor ID
2 Byte
R
e
a
d
o
n
ly
08
hex
09
hex
Device ID
3 Byte
0A
hex
0B
hex
10
hex
0
Vendor Name
8 Byte
11
hex
0
Vendor text
16 Byte
12
hex
0
Product Name
34 Byte
13
hex
0
Product ID
21 Byte
14
hex
0
Product text
34 Byte
16
hex
Hardware Revision
3 Byte
17
hex
0
Firmware Revision
3 Byte
Identification data
Type
Device ID
Version
BNI IOL-710-000-K006
050201hex
Voltage version
BNI IOL-709-000-K006
050202hex
Current version