www.balluff.com
13
english
3
Configuration via Explicit Messages (continued)
3.4
Fault State
For each output at the port pins, a safe state can be
pre-defined, which should be adopted in the case of a loss
of bus communication.
The
Fault State
settings can be implemented via the
following Class Instance Attribute of the
Explicit Messages
.
Activate / deactivate Fault State
Class
Instance Attribute
Value
9 (0x09) 1 – m
1)
6
0: Fault State
disabled
1: Fault State
enabled
1)
m: Number of outputs
Tab. 3-3: Values for
Fault State –
Activation/Deactivation
Fault State Action
Class
Instance Attribute
Value
9 (0x09) 1 – m
1)
5
0: Output on
1: Hold last state
1)
m: Number of outputs
Tab. 3-4: Values for
Fault State – Fault State Action
The
Fault State
settings are only stored temporarily
in the module. They are deleted again after a
power reset.
In order to ensure a permanent
Fault State
configuration, the configuration must be
programmed via the PLC so that it can be
transferred to the module again when the system
is restarted.
Discrete Output Current Value
Class
Instance Attribute
Value
9 (0x09) 1 – m
1)
100
1: 1 A
2: 2 A
4: 4 A
2)
1)
m: Number of outputs
2)
Only for Pin 2
Tab. 3-5: Values for
Discrete Output Current Value
BNI EIP-508-105-Z067
Network interface
Содержание BNI EIP-508-105-Z067
Страница 1: ...deutsch Konfigurationsanleitung english Configuration Guide BNI EIP 508 105 Z067 ...
Страница 2: ...www balluff com ...
Страница 3: ...BNI EIP 508 105 Z067 Konfigurationsanleitung deutsch ...
Страница 4: ...www balluff com ...
Страница 45: ...BNI EIP 508 105 Z067 Configuration Guide english ...
Страница 46: ...www balluff com ...
Страница 87: ......