Balluff BIC 1I0-IAA50-M30MI3-SM4A4A Скачать руководство пользователя страница 1

IO-Link System 
BIC 1I0-IAA50-M30MI3-SM4A4A,  
BIC 2I0-IAA50-M30MI3-SM4A5A 
BIC 2I0-IAA50-M30MI3-BPX04-002-M45A 

 

Safety Informations 

Intended use 

This guide describes the 

B

alluff 

I

nductive 

C

oupling 

System 

BIC

 

… for the use in industrial environment 

consisting of 

Base 

unit and 

Remote

 unit.  

The electrical power is provided to the Remote unit via 
air gap. Simultaneously data are transmitted in IO-Link 
format. 
The Base unit communicates via IO-Link protocol with 
the host IO-Link master unit. The Remote unit is working 
as a virtual IO-Link master unit to the connected IO-Link 
device. 
 

 

Read this operating guide thoroughly before 
startup! 
These sensors may not be used in 
applications where the safety of persons 
depends on device function (not a safety 
component per the EU Machine Directive). 

 

 

Caution! 

Risk of burning on hot surfaces! 
The active surface heats up even under 
normal operating conditions. 
Keep away hands and objects from the active 
surface. 
Avoid contact of metal objects on the active 
surface. Fire hazard! 

 

Approved personnel 

Installation and startup are permitted only by trained 
specialists. 
 

Improper Use 

Damage resulting from unauthorized actions or improper 
use is not covered under the warranty and liability 
provisions. 
 

Obligations of the operator! 

The equipment is an EMC Class A product. Such 
devices may cause RF noise radiation. The operator 
must take appropriate measures to account for this. 
The operator is responsible for observing the locally 
prevailing safety regulations. 
 

Fault conditions 

When defects and non-clearable faults occur in the 
device, it must be taken out of service and secured 
against unauthorized use. 
 
 
 
 
 
 
 
 

Installation 

Mutual interference 

To prevent mutual interference from other Base or 
Remote units, maintain the following separation 
distances. 
 

 

Type 

A (mm) 

BIC 1I0-IAA50...SM4A4A 

100 

BIC 2I0-IAA50...SM4A5A 

100 

BIC 2I0-IAA50-M30MI3-BPX04-002-M45A 

 

100

 

 
Installation in metal 

When installing in metal the specified minimum distances 
from the surrounding sides of the metallic object must be 
maintained, since otherwise the transmission distance 
between Base and Remote will change. The 
transmission distance can also be affected by the type of 
metal. 
 

Type 

A (mm) 

B (mm) 

BIC 1I0-IAA50...SM4A4A 

30 

20 

BIC 2I0-IAA50...SM4A5A 

30 

20 

BIC 2I0-IAA50-M30MI3-BPX04-002-M45A

 

30 

20 

 

 

 

Distance D  

in mm 

Angle X 

in ° 

18° 

12° 

10° 

5° 

0° 

 

IO-Link Communication 

Transmission rate 

COM2 (38,4 kBaud) 

Frame type 

Min cycle time 

3 ms 

Process data cycle 

< 200 ms  

SIO Mode 

no 

IO-Link Revision 

1.0 

Masterporttyp 

Processdata in 

11 

Processdata out 

 

Errors 

Error Code 

Additional Code 

device application error 

Index not available 

0x80 

0x11 

device application error 

SubIndex not available 

0x80 

0x12 

 