30
english
Index
Sub-
index
Access
Description
Data
type
Value
range
Default
value
VIBRATION SEVERITY ZONE CONFIGURATION
0x2108
(8456)
0x01
(1)
Read/Write SEVERITY ZONE BOUNDARY A/B – RMS value at
which the vibration changes between degrees of
severity A and B. Value in mm/s.
float32
0…12500
[mm/s]
12500
[mm/s]
0x02
(2)
Read/Write SEVERITY ZONE BOUNDARY B/C – RMS value at
which the vibration changes between degrees of
severity B and C. Value in mm/s.
float32
0…12500
[mm/s]
12500
[mm/s]
0x03
(3)
Read/Write SEVERITY ZONE BOUNDARY C/D – RMS value at
which the vibration changes between degrees of
severity C and D. Value in mm/s.
float32
0…12500
[mm/s]
12500
[mm/s]
0x04
(4)
Read/Write ENABLE SEVERITY ZONE CHANGE EVENT –
Activates (True) or deactivates (False) the sending of
the IO-Link event (0x8CF0) in case the severity zone
changes. The severity zone boundaries can be
configured in subindices 0x01 (1) through 0x03 (3).
bool
True/False
True
VIBRATION VELOCITY ADVANCED ALARM STATUS
0x2111
(8465)
0x01
(1)
Read only
PRE-ALARM STATUS v-RMS X – The pre-alarm
threshold for the RMS value of the X-axis has (True) or
has not (False) been exceeded.
bool
0x02
(2)
Read only
MAIN-ALARM STATUS v-RMS X – The main-alarm
threshold for the RMS value of the X-axis has (True) or
has not (False) been exceeded.
bool
0x03
(3)
Read only
PRE-ALARM STATUS v-RMS Y – The pre-alarm
threshold for the RMS value of the Y-axis has (True) or
has not (False) been exceeded.
bool
0x04
(4)
Read only
MAIN-ALARM STATUS v-RMS Y – The main-alarm
threshold for the RMS value of the Y-axis has (True) or
has not (False) been exceeded.
bool
0x05
(5)
Read only
PRE-ALARM STATUS v-RMS Z – The pre-alarm
threshold for the RMS value of the Z-axis has (True) or
has not (False) been exceeded.
bool
0x06
(6)
Read only
MAIN-ALARM STATUS v-RMS Z – The main-alarm
threshold for the RMS value of the Z-axis has (True) or
has not (False) been exceeded.
bool
0x07
(7)
Read only
PRE-ALARM STATUS v-RMS MAGNITUDE – The
pre-alarm threshold for the RMS value of the
magnitude has (True) or has not (False) been
exceeded.
bool
0x08
(8)
Read only
MAIN-ALARM STATUS v-RMS MAGNITUDE – The
main-alarm threshold for the RMS value of the
magnitude has (True) or has not (False) been
exceeded.
bool
6
IO-Link interface (continued)
BCM R15E-00 _ -DI00-_ _ , _-S4
Condition Monitoring Sensor
Содержание BCM R15E-00 Series
Страница 1: ...BCM R15E 00_ DI00 _ _ _ S4 deutsch Betriebsanleitung english User s guide...
Страница 2: ...www balluff com...
Страница 3: ...BCM R15E 00_ DI00 _ _ _ S4 Betriebsanleitung deutsch...
Страница 4: ...www balluff com...
Страница 49: ...BCM R15E 00_ DI00 _ _ _ S4 User s Guide english...
Страница 50: ...www balluff com...
Страница 95: ......