IO-Link interface (continued)
Tab. 6-6 provides an overview of the possible parameters
that can be applied in the process data by means of the
user-defined process data profile. For this purpose, the
specified four bytes must be written to the subindex of the
slot of index 0x2001 (8193) to be configured.
PARAMETER NAME
Byte 0
Byte 1
Byte 2
Byte 3
Contact temperature
CONTACT TEMPERATURE
0x20 (32)
0x31 (49)
0x01 (1)
0x00 (0)
Relative humidity
HUMIDITY
0x20 (32)
0x41 (65)
0x01 (1)
0x00 (0)
Ambient pressure
AMBIENT PRESSURE
0x20 (32)
0x49 (73)
0x01 (1)
0x00 (0)
Vibration
v-RMS X
0x21 (33)
0x14 (20)
0x01 (1)
0x00 (0)
v-RMS Y
0x02 (2)
v-RMS Z
0x03 (3)
v-RMS magnitude
0x04 (4)
v-PEAK-TO-PEAK X
0x15 (21)
0x01 (1)
v-PEAK-TO-PEAK Y
0x02 (2)
v-PEAK-TO-PEAK Z
0x03 (3)
v-PEAK-TO-PEAK magnitude
0x04 (4)
v-MEAN X
0x18 (24)
0x01 (1)
v-STANDARD DEVIATION X
0x02 (2)
v-CREST FACTOR X
0x03 (3)
v-SKEWNESS X
0x04 (4)
v-KURTOSIS X
0x05 (5)
v-MEAN Y
0x19 (25)
0x01 (1)
v-STANDARD DEVIATION Y
0x02 (2)
v-CREST FACTOR Y
0x03 (3)
v-SKEWNESS Y
0x04 (4)
v-KURTOSIS Y
0x05 (5)
v-MEAN Z
0x1A (26)
0x01 (1)
v-STANDARD DEVIATION Z
0x02 (2)
v-CREST FACTOR Z
0x03 (3)
v-SKEWNESS Z
0x04 (4)
v-KURTOSIS Z
0x05 (5)
a-RMS X
0x1D (19)
0x01 (1)
a-RMS Y
0x02 (2)
a-RMS Z
0x03 (3)
a-RMS magnitude
0x04 (4)
a-PEAK-TO-PEAK X
0x1E (30)
0x01 (1)
a-PEAK-TO-PEAK Y
0x02 (2)
a-PEAK-TO-PEAK Z
0x03 (3)
a-PEAK-TO-PEAK magnitude
0x04 (4)
Tab. 6-6: Possible indices for process data
BCM R15E-00 _ -DI00-_ _ , _-S4
Condition Monitoring Sensor
Содержание BCM R15E-00 Series
Страница 1: ...BCM R15E 00_ DI00 _ _ _ S4 deutsch Betriebsanleitung english User s guide...
Страница 2: ...www balluff com...
Страница 3: ...BCM R15E 00_ DI00 _ _ _ S4 Betriebsanleitung deutsch...
Страница 4: ...www balluff com...
Страница 49: ...BCM R15E 00_ DI00 _ _ _ S4 User s Guide english...
Страница 50: ...www balluff com...
Страница 95: ......