14
english
BAE PS-XA-3Y-24-250-609-I / BAE PS-XA-3Y-24-250-611-I
Power supply units
5.1
Installation
For dimensions, see Fig. 4-1 on page 8.
CAUTION
Sharp edges
Sharp edges on the back can cause injuries.
►
Place the device on a sufficiently large, level surface.
5.1.1 Wall mounting
►
Preferably mount the device with the outputs facing
down (standard orientation) on a flat surface using
4 screws at the upper and lower mounting holes. The
recommended screw size is M4.
5.1.2 Mounting orientation
Standard orientation
IN IOL OUT
Power supply unit
Fig. 5-1:
350
500
600
0
+45 +55
+70
Output power [W]
Ambient temperature [°C]
Permissible output power (standard orientation)
5
Installation and connection
Alternative mounting orientations
Alternative mounting orientations require a
reduction in output power.
Upside down
IN
IOL
OUT
Power supply unit
Horizontal
IN
IOL
OUT
Power supply
unit
IN
IOL
OUT
Power supply
unit
Overhead mounting and on the table
Power supply unit
Power supply unit
Fig. 5-2:
350
500
0
+45
+60
Output power [W]
Ambient temperature [°C]
Permissible output power (alternative orientations)
Содержание BAE PS-XA-3Y-24-250-609-I
Страница 1: ...BAE PS XA 3Y 24 250 609 I BAE PS XA 3Y 24 250 611 I deutsch Betriebsanleitung english User s Guide...
Страница 2: ...www balluff com...
Страница 3: ...BAE PS XA 3Y 24 250 609 I BAE PS XA 3Y 24 250 611 I Betriebsanleitung deutsch...
Страница 4: ...www balluff com...
Страница 25: ...BAE PS XA 3Y 24 250 609 I BAE PS XA 3Y 24 250 611 I User s Guide english...
Страница 26: ...www balluff com...
Страница 47: ......