www.baldormotion.com
5-24 Operation
MN1941
5. To repeat the tests for negative (reverse) demands, type:
TORQUEREF(0)=-5
This should cause a demand of -5% of maximum output (-0.5 V) to be produced at the
DEMAND0 output. Correspondingly, the Spy window’s Velocity display should show a
negative value.
6. To remove the demand and stop the test, type:
STOP(0)
This should cause the demand produced at
the DEMAND0 output to become 0 V.
If it is necessary for the motor to turn in the opposite direction for a positive demand, then the
DACMODE
and
ENCODERMODE
keywords should be used. The
DACMODE
keyword is used to
invert the demand output voltage. The
ENCODERMODE
keyword must then also be used to
reverse the incoming feedback signal, to correspond with the inverted demand output. Note that
if
ENCODERMODE
had
already
been used to compensate for a reversed encoder count (as
described in step 4. above), it will be necessary to change it back to its original setting to
correspond with the inverted demand output set using
DACMODE
. Whichever keywords are used,
for the control system to operate correctly, a positive demand must result in a positive change in
position and a negative demand must result in a negative change in position.
See the Mint help file for details of each keyword.
Содержание NXE100-1608Dx
Страница 1: ......
Страница 2: ......
Страница 16: ...www baldormotion com 3 4 Basic Installation MN1941 ...
Страница 50: ...www baldormotion com 4 34 Input Output MN1941 ...
Страница 77: ...www baldormotion com Operation 5 27 MN1941 Figure 37 The NextMove e100 servo loop ...
Страница 98: ...www baldormotion com 6 8 Troubleshooting MN1941 ...
Страница 110: ...Index MN1941 ...
Страница 112: ...Comments MN1941 Thank you for taking the time to help us ...
Страница 113: ......
Страница 114: ......