background image

Section

3–9

MN1229

Encoder Output 

The encoder output provides position information to the host position controller.
Use twisted pair shielded cable with an insulated overall shield.  Connect the
Encoder Output signals to the positioner as follows: (See Figure 3-6).

Figure 3-6  Encoder Output

X7

Channel B

Channel A

GND

Channel A

Channel C

1

2

3

5

4

6

8

7

9

Channel C

Channel B

1.

Connect the Channel A to X7-1 and Channel A to X7-6.

2.

Connect the Channel B to X7-2 and Channel B to X7-7.

3.

Connect the Channel C to X7-3 and Channel C to X7-8.

4.

Connect the GND to X7-5.

The encoder resolution must be set as described in the software manual.

Содержание DBSC105-AAA-1

Страница 1: ...25 00 DBSC 100 Series AC Servo Control 9 96 MN1229 Installation and Operating Manual AC Servo Drive...

Страница 2: ...2 Signal Levels 2 4 Regeneration 2 5 Operating Conditions 2 5 Optional 24VDC Input 2 5 Section 3 Installation 3 1 Overview 3 1 Location and Mounting 3 1 Altitude Derating 3 1 Temperature Derating 3 1...

Страница 3: ...Control Inputs 3 12 Control Outputs 3 12 Electronic Handwheel Optional 3 13 Cable Preparation 3 13 Cable Connection 3 14 Section 4 System Setup 4 1 Overview 4 1 DIP Switch Settings 4 1 Jumper Settings...

Страница 4: ...cribed in EN 60204 and VDE 0160 This means use DBSC100 in stationary ground based applications only It is a component only and is not intended for immediate use within the meaning of Safety law of app...

Страница 5: ...nd removal inconvenience or consequential damage including injury to any person or property caused by items of our manufacture or sale Some states do not allow exclusion or limitation of incidental or...

Страница 6: ...ment to which it is connected Electrical shock can cause serious or fatal injury Only qualified personnel should attempt the start up procedure or troubleshoot this equipment WARNING Be sure that you...

Страница 7: ...uring control failure WARNING Motor circuit may have high voltage present whenever AC power is applied even when motor is not rotating Electrical shock can cause serious or fatal injury Caution To pre...

Страница 8: ...n with RS 422 RS485 Electronic Handwheel Pulse Follower with RS 232 Electronic Handwheel Pulse Follower with RS 422 RS485 Code Feedback Options A B Standard Resolver Encoder Code Field Bus Options A B...

Страница 9: ...17 Efficiency 97 Minimum Load Inductance mH 400 Nominal Switching Frequency KHz 8 5 Mounting Panel Overall Dimensions in mm 2 65x6 81x6 67 5x173x152 5 3 6x6 8x6 92 5x173x152 5 Weight lbs Kg 2 73 1 24...

Страница 10: ...Efficiency 97 Minimum Load Inductance mH 400 Nominal Switching Frequency KHz 8 5 Mounting Panel Overall Dimensions in mm 2 65x6 81x6 67 5x173x152 5 3 6x6 8x6 92 5x173x152 5 Weight lbs Kg 2 73 1 24 wi...

Страница 11: ...ty 1500 RPM Velocity 6000 RPM Velocity 6000 RPM bits 16 14 12 Resolver Pole Paris 1 Resolver Winding Ratio 0 5 Encoder Output RS422 Encoder Resolution ppr 512 10241 2048 4096 Pulse Direction Input RS4...

Страница 12: ...tion Unit DBSC 102 DBSC 105 Ambient Operating Temperature C 5 to 40 Humidity 10 to 90 RH Non Condensing According to DIN40 040 class F Altitude m 1000 Shock 10G DIN IEC 68 2 6 29 Vibration 1G DIN IEC...

Страница 13: ...osition with connector X1 at the top using the mounting hole s provided Mounting hole location is shown in Section 6 of this manual The area selected should allow air to freely circulate around the co...

Страница 14: ...separate from power wiring The use of shielded wire is recommended for all control wiring Protective Devices Be sure a suitable input power protection device is installed Slow Blow Fuse Each DBSC mus...

Страница 15: ...00 Connector Locations Monitor Off On AS1 Ready X1 PE L N U V W DB DB 24v 0v X2 1 2 3 4 5 6 7 8 X 9 X 6 X 7 X 3 DB On X 8 Optional Hardware Encoder Input Serial Interface Encoder Output Resolver Input...

Страница 16: ...F is connected to GND When a control input is at 24VDC range 12VDC to 29VDC it is active and when it is at GND it is inactive Figure 3 2 shows this relationship Active Low Definition If the Control In...

Страница 17: ...16 and 17 are optional inputs and are described later in this section A typical wiring control diagram is shown in Figure 3 3 1 Connect the CREF signal wire to X3 7 2 Connect the Enable signal wire t...

Страница 18: ...5 6 7 8 9 10 11 12 14 13 15 16 17 18 19 20 Optional External Power Source 24VDC GND CREF Enable CW Limit CCW Limit Hold Reset Pulse Input Direction Input Machine Input 1 Machine Input 2 Machine Outpu...

Страница 19: ...2 3 AGND CMD Single Ended Input 1 Determine if your application requires Single Ended Input Step 2 or Differential Input Step 3 Command Signal wiring 2 For Single Ended Input wiring A Connect the CMD...

Страница 20: ...ector X1 8 Resolver Wiring The Resolver interface DB 9 connector is X8 on the DBSC control Figure 3 5 shows the connector pin numbers and signal names Use twisted pair shielded cable with an insulated...

Страница 21: ...to the positioner as follows See Figure 3 6 Figure 3 6 Encoder Output X7 Channel B Channel A GND Channel A Channel C 1 2 3 5 4 6 8 7 9 Channel C Channel B 1 Connect the Channel A to X7 1 and Channel...

Страница 22: ...orted by the DBSC control Mode is jumper selectable as described in Section 4 of this manual RS422 RS485 Not available in model DBSC 10X AXX RS422 RS485 is a factory installed and jumper selectable in...

Страница 23: ...3 8 Optional External Fault Indicator X3 4 5 Voltage Source Customer Supplied Fault Circuit 24VDC External Power Source Optional Caution To prevent equipment damage DO NOT connect a 24VDC source to te...

Страница 24: ...the Direction Input signal to X3 15 Control Outputs Optional Four Opto Isolated outputs are available for Active Low Sink use Connect one or more of the control outputs as follows see in Figure 3 9 1...

Страница 25: ...22 AWG 0 34mm2 wire to the braided shield Carol cable has a clear Mylar sleeve between the braided shield and the wire bundle Belden cable does not have a Mylar sleeve 3 Connect all shields to X9 13...

Страница 26: ...Channel A X9 1 A Channel A X9 6 A Channel B X9 2 B Channel B X9 7 B Channel C X9 3 C Channel C X9 8 C Encoder Supply 5VDC X9 11 Ground Return X9 13 2 Single Ended Connections Only Differential inputs...

Страница 27: ...tion to the left represents a 0 indicated in the table The ON position to the right represents a 1 indicated in the table For example if the card address is 3 Table 4 1 indicates the switch settings s...

Страница 28: ...Switch AS1 5 has no function It may be placed in either position 2 Place switch AS1 6 in the correct position Applicable only in the Velocity mode In the ON position the motor will quickly decelerate...

Страница 29: ...ct jumper positions for that mode Table 4 3 Jumper Setting Configuration Jumpers Function Jumper Position Option SB 601 609 RS232 1 2 Axx Exx Fxx SB 601 609 RS422 or 485 2 3 Bxx Exx Fxx Indicates fact...

Страница 30: ...time power up condition 1 Disconnect the motor leads from X1 U X1 V and X1 W The initial adjustments must be performed under a no load condition 2 Control must be disabled X3 9 input Figure 3 3 switch...

Страница 31: ...e ended abnormally or the decimal point is ON refer to the troubleshooting section of this manual 8 If the Ready LED is green and ON and the Monitor display shows the letter d the control is ready to...

Страница 32: ...resistor Input voltage too high Red 3 Over current fault More than 2X peak current Motor leads shorted or control failure Red 4 Over or Under voltage fault Internal 15VDC supply fault Red 5 Resolver...

Страница 33: ...vated by hardware or software Green d Control Disabled Disable mode activated by hardware or software Red U EEPROM fault Reset control Green J Jog mode Jog mode activated by hardware or software Green...

Страница 34: ...Section 6 Drawings 6 1 MN1229 DBSC Dimensions...

Страница 35: ...A 2 CHB Channel B 3 CHC Channel C 4 SYNC U 5 SYNC U 6 CHA 7 CHB 8 CHC 9 SYNC W 10 SYNC V 11 5V 12 No Connection 13 DGND 14 SYNC W 15 SYNC V X6 Interface 1 No Connection 2 RXD 3 TXD 4 DTR 5 DGND 6 DSR...

Страница 36: ...29 Mounting Hole Location Heat Sink Rear View 2 5 2mm 6 028 153mm Location of mounting hole Locate and drill hole in enclosure Mount control to enclosure Alternate mounting using two 2 tabs and four 4...

Страница 37: ...BALDOR ELECTRIC COMPANY P O Box 2400 Fort Smith AR 72902 2400 501 646 4711 Fax 501 648 5792 Baldor Electric Company Printed in USA MN1229 9 96 C J2500...

Отзывы: