54464_02-97_A

DIP Switches and Jumpers Definitions

DIP Switchbank A Key

A1

  . . . . . . . . . . . . . . . . Test Mode (normally Off)

A2

  . . . . . . . . . . . . . . . . In “ON” position, heater can run while any/all high-speed pumps or blowers are running

  

(High 

amperage)

  . . . . . . . . . . . . . . . . In “OFF” position, heater is disabled while any high-speed pump or blower is running

  

(Low 

amperage)

A3

  . . . . . . . . . . . . . . . . In “ON” position, filter cycles are programmed by duration for non-time capable panels
  . . . . . . . . . . . . . . . . In “OFF” position, filter cycles are programmed to start and end times for time capable panels

A4*

  . . . . . . . . . . . . . . . . In “ON” position, displays time in 24 hours (military\European time)
  . . . . . . . . . . . . . . . . In “OFF” position, displays 12 hour time

A5*

  . . . . . . . . . . . . . . . . In “ON” position, displays temperature in Celsius
  . . . . . . . . . . . . . . . . In “OFF” position, displays temperature in Fahrenheit

* Sets default for user preferences - only applies when persistent memory is reset (A12 On) during power-up

A6

  . . . . . . . . . . . . . . . . In “ON” position, Equipment timeout 30 minutes (4 hours for Pump 1-Low)
  . . . . . . . . . . . . . . . . In “OFF” position, Equipment timeout 15 minutes (2 hours for Pump 1-Low)

A7

. . . . . . . . . . . . . . . . In “ON” position, Cleanup Cycle – 30 minutes after spa use/timeout, Pump 1-Low & Ozone or 

 

 

Circ Pump and Ozone run for 1 hour

  . . . . . . . . . . . . . . . . In “OFF” position, no Cleanup Cycle

A8

  . . . . . . . . . . . . . . . . In "ON" position, Ozone suppression for one hour after pump/blower button press

A9 and A10. . . . . . . . . . . . . See 

Table

 for Circ Pump Behavior settings

A11

. . . . . . . . . . . . . . . . In “ON” position

 

 

(non-circ mode operation) 

Pump 1 is two-speed, Ozone is

 

 

ON in Filter & Cleanup Cycles only

 

 

(in any circ mode) 

Pump 1 is one-speed, Ozone is ON with

  

circ 

pump

  . . . . . . . . . . . . . . . . In “OFF” position

 

 

(non-circ mode operation)

 Pump 1 is two-speed, Ozone is

 

 

ON with Pump 1-Low

 

 

(in any circ mode)

 Pump 1 is two-speed, Ozone is ON with

  

circ 

pump

A12

  . . . . . . . . . . . . . . . . Persistent memory reset (normally off) (used when spa is 

  

powering 

up)

   

 

Circ Pump 

A9

A10

Behavior

OFF

OFF

No Circ Pump

   

 

or Circ Pump not 

  

 

plumbed 

w/heater

ON

OFF

24 Hours

OFF

ON

24 Hr w/3°F Shut-Off

ON

ON

Acts like Pump 1-Low

   

 

(Filter Cycles, Polls)

Jumpers

J37

Jumper on Pins 1 and 2 will power one leg of J12 (Spa Light) at 120 Volts AC.
Jumper on Pins 2 and 3 will power one leg of J12 (Spa Light) at 12 Volts AC.

Note: W9 controls voltage on the other leg of J12 and must be set for the same voltage.

J91

Jumper on 1 Pin only enables Real Time Clock function; use with time capable panels.
Jumper on Pins 1 and 2 disables RTC function; use with non-time capable panels.

DIP Switchbank B Key

B1

. . . . . . . . . . . . . . . In “ON” position, single-speed Pump 2
. . . . . . . . . . . . . . . In “OFF” position, two-speed Pump 2

B2

. . . . . . . . . . . . . . . In “ON” position, Pump 2 enabled
. . . . . . . . . . . . . . . In “OFF” position, Pump 2 disabled

B3

. . . . . . . . . . . . . . . In “ON” position, Blower enabled with Pump 2 low relay
. . . . . . . . . . . . . . . In “OFF” position, Blower disabled

B4

. . . . . . . . . . . . . . . In “ON” position, Fiber and Wheel instead of Spa Light

         (if A9 & A10 are both OFF, Fiber uses J2 connector; if either A9 or A10 is ON, X-FOW Kit required to run Fiber)

. . . . . . . . . . . . . . . In “OFF” position, Spa light enabled

B5

. . . . . . . . . . . . . . . In “ON” position, Pump 3 enabled (Jets 3 replaces Blower on Aux panel)
. . . . . . . . . . . . . . . In “OFF” position, Pump 3 disabled

B6

. . . . . . . . . . . . . . . In “ON” position, Alternate Panel layout (ML900 scrunching enabled - ML550 / 700 Jets 3 replaces Blower)
. . . . . . . . . . . . . . . In “OFF” position, Normal Panel layout

WARNING:

Setting DIP switches incorrectly may cause abnormal system behavior and/or damage to system components.

Refer to Switchbank illustration on Wiring Configuration page for correct settings for this system.

Contact Balboa if you require additional configuration pages added to this hot sheet.

Содержание E2P-EL2001M3-YCAJ

Страница 1: ...A pdf 11 27 2006 Template used 40573 v28_A pdf 11 22 2006 9XcYfX ejkild ekj Jpjk d GE System Model E2P EL2001M3 YCAJ Software Version 28 EPN 2130 Base PCBA PN 53974 03 PCB EL2000 PN 22896 Rev B Base P...

Страница 2: ...eo System Connects to A V terminal J4 U4 ADCM W12 MAIN PANEL MAIN PANEL MAIN PANEL AUX PANEL AUX PANEL J6 J3 W2 REMOTE J86 J80 J69 J20 J10 J39 J71 J70 J17 J15 J13 J83 J22 J24 J82 J36 SENS A SENS B VAC...

Страница 3: ...is must be corrected before you can reset Persistent Memory The switch numbers jumpers or configuration settings displayed after are ones with which the system has found a configuration problem For ex...

Страница 4: ...n and DIP Settings Setup 1 As Manufactured 240V Pump 1 2 Speed 240V Pump 2 2 Speed 240V Blower 240V Circ Pump 120V Ozone 12V Spa Light 120V Audio Visual Stereo 240V 4 0kW Heater ML900 ML700 or ML400 M...

Страница 5: ...mode Pump 1 is two speed Ozone is ON with circ pump A12 Persistent memory reset normally off used when spa is powering up Circ Pump A9 A10 Behavior OFF OFF No Circ Pump or Circ Pump not plumbed w heat...

Страница 6: ...1 2 3 4 5 6 7 8 9 RED AC WHT AC J53 J23 J19 J43 J48 K12 U4 J50 J52 BLK AC J66 J65 J63 J64 J42 J54 J56 J55 J25 J57 J26 TB1 CLASS G FUSE 30A CLASS G FUSE 30A F6 F7 F4 K4 W1 F2 K7 T1 HTR2 HTR1 FUSE 0 3A...

Страница 7: ...n replace the X P in cases where branch circuit protection is needed for high amperage devices that would over burden power input fuse F7 1 B on the main PCBA This allows J6 on the X P231 to connect d...

Страница 8: ...determines voltage Ozone Connector Voltage The EL circuit board is factory configured to deliver a preset voltage 120V or 240V to the on board ozone connector J9 See the ratings table on the wiring d...

Страница 9: ...er J91 on Main PCBA must be OFF 1 pin only Heat Jets Aux Temp Light ML400 PN 52684 with Overlay PN 11345 Connects to Main Panel terminal J70 J71 or J72 RTC Jumper J91 on Main PCBA must be ON both pins...

Отзывы: