5. Identify and correct errors and select RESET to return to the prior mode (without
removing error messages from memory).
Figure 35 FAILSAFE Menu
To prevent the valve from moving after reset, put the controller in manual, and set the
valve position setpoint to the failsafe position 0% if ATO, 100% if ATC. You can set a
special case of FAILSAFE. You can set a Position Error Band and a Position Error Time 2
that forces the valve to its failsafe position if the position error exceeds the band for a time
longer than time 2. This can be used on critical loops to force the process to trip if the
positioner is unable to control the valve.
RESET
+
+
FAILSAFE Menu
FAILSAFE
*
CLR ERR
+
+
VIEW ERR
MANUAL MODE
MANUAL
CYCLING MENU
Clears
Errors
*
*
*
Pressing *
displays the first
error, pressing a second time
displays the second error.
Keep pressing to see all errors
until VIEW ERR appears.
WAIT
Quickly Flashes