Calibration
CAUTION
Pilot Trim Valve Applications require the use of the
Manual Stop calibration procedure (refer to Configura-
tion and Calibration of the SVI II AP Instruction Man-
ual, GEA19681). Do not run Find Stops or the ValVue
Setup Wizard on valves with Pilot Trim or damage to
the valve will occur.
To calibrate the SVI II AP:
1. Observe the display following power-up. The SVI II AP
powers up in the previously active mode either MANUAL or
NORMAL (operating) mode:
In NORMAL mode, the display alternates between POS
and SIGNAL.
In MANUAL, the display alternates between POS –M
and SIG.
2. With
MANUAL
mode displayed, press
*
to select the
MANUAL mode.
3. Press
+
again;
CONFIG
appears. Pressing
+
again brings
CALIB
.
4. Select
CALIB
by pressing
*
. STOPS appears. The valve
moves full open and back to full closed. Observe all
warnings.
5. Press
*
to cause the valve to stroke and to automatically
calibrate valve travel.
6. After the
STOPS
procedure finishes, press
+
twice until
TUNE
appears.
Содержание Masoneilan SVI II AP Series
Страница 6: ...This page intentionally left blank ...
Страница 76: ...This page intentionally left blank ...
Страница 82: ...This page intentionally left blank ...
Страница 105: ...Masoneilan SVI II AP Digital Positioner Quick Start Guide 105 2020 Baker Hughes Company All rights reserved ...
Страница 106: ... 2020 Baker Hughes Company All rights reserved Masoneilan SVI II AP Digital Positioner Quick Start Guide 106 ...
Страница 108: ...This page intentionally left blank ...
Страница 122: ...This page intentionally left blank ...
Страница 123: ...This page intentionally left blank ...