SECTION 4 - CALIBRATION
INTRODUCTION
This section identifies the calibration status of the unit and
provides the calibration check procedures. Calibration and
validation procedures using both the Type STT terminal and
the EZ CAL option appear here.
CALIBRATION PROCEDURES
If the standard configuration is ordered, the Type PTSDL level
transmitter will be set close to a zero based full scale span. A
custom calibration can be factory supplied or implemented in
the field.
The Type PTSDL level transmitter operates in either the analog
mode or the digital mode. Calibration procedures differ
depending on the selected mode of operation.
The
analog
mode of operation allows both a complete bench
calibration and a D/A adjustment. The D/A adjustment com-
pensates for slight inaccuracies in the four to 20-milliampere
current loop (or in receiving devices such as recorders). Use
this procedure only when the system has first been installed or
if something in the four to 20-milliampere current loop has
changed. The
digital
mode of operation allows only a bench
calibration.
NOTE: This section is meant as a generalized guide and does not
go through the step-by-step procedures required of the
Type STT terminal. Although the menus that appear on the Type
STT terminal display are easy to follow, the
mitter Terminal Instruction should be consulted while performing
these procedures.
Equipment Required for Calibration
•
DC power supply, 24,
±
1 VDC (recommended).
•
Digital multimeter (DMM) - 4-½ digit display minimum
with an accuracy at least four times greater than that of
the transmitter (Table
).
WARNING
Explosionproof/dust-ignitionproof installations and intrinsi-
cally safe installations in Class II or Class III hazardous loca-
tions require that the assembly be kept tight while circuits are
live unless the location is known to be nonhazardous at the
time.