INSTALLATION
SETUP/PHYSICAL INSTALLATION
I-E96-403A
2 - 3
Cable Connections
The NTAI02 has five cable connectors. Connector P1 and P2
connect separate NKTU01/11 TU cables to two slave modules
for input signal routing. Connector P3 is only used for full scale
calibration of IMASM02 modules connected to P1 and P2. Con-
nector P4 is labeled IN and connects to the IMAMM03 or
NTAM01, or it can be used to interconnect from another
NTAI02 through the NKAI01 cable. Connector P5 is labeled
OUT and connects to another NTAI02.
The NKTU01/11 is a round, shielded cable that connects the
TU to the IMASM02 slave module or IMAMM03 master module.
The NKTU01 and NKAI01 cables have a PVC jacket rated for 80
degrees celsius at 300 volts (UL rated type CL2). The NKTU11
and NKAI01 cables have a non-PVC jacket rated for 90 degrees
celsius at 300 volts (UL rated type PLTC). The NKAI01 cable is
a round, shielded cable that connects the TU to an NTAM01 TU
when redundant IMAMM03s are used or to another NTAI02
TU. See Figure
for the cable connections from the termina-
tion unit to the slave modules. Table
lists the NTAI02 cable
applications.
Figure 2-1. Installation for NTAI02
TB1
TB2
TB3
TB4
TB4
TB3
TB2
TB1
FIELD TERMINATION PANEL
MOUNTING SCREWS
T00464A
TABS
STANDOFF