IMLMM02 LOGIC MASTER MODULE CONFIGURATION
INTRODUCTION
I - 2
I-E96-410A
®
Table I-1. IMLMM02 Switch S2 (Run Mode)
Switch Position
Function
1
2
3
0
0
0
Normal mode, normal run
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.
Table I-2. IMLMM02 Switch S2 (Module Address)
Address
Example
Switch Position
(Binary Value)
4
(16)
5
(8)
6
(4)
7
(2)
8
(1)
0
0
0
0
0
0
8
0
1
0
0
0
16
1
0
0
0
0
24
1
1
0
0
0
31
1
1
1
1
1
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.
Table I-3. IMLMM02 Jumpers J1 through J8
(Digital Input Type)
Jumper
Position
Digital Input Type
1-2
125 VDC or 120 VAC
2-3
24 VDC