Process Control and
Automation Solutions
from Elsag Bailey Group

E96-308

Pulse Input Slave Module

(IMDSM04)

Содержание Infi 90 IMDSM04

Страница 1: ...Process Control and Automation Solutions from Elsag Bailey Group E96 308 Pulse Input Slave Module IMDSM04...

Страница 2: ...UIPEMENTS LECTRONIQUES SONT SENSIBLES AUX PERTURBATIONS PAR FR QUENCE RADIO DES PR CAUTIONS DEVRONT TRE PRISES LORS DE L UTILISATION DU MAT RIEL DE COMMUNICATION PORTATIF LA PRUDENCE EXIGE QUE LES PR...

Страница 3: ...instruction explains the slave module features specifica tions and operation It details the procedures you must follow to set up and install an IMDSM04 module and explains status indicators that help...

Страница 4: ...h 5 2 Original 6 1 Original 7 1 Original 8 1 Original A 1 through A 3 Original B 1 through B 3 Original When an update is received insert the latest changed pages and dispose of the super seded pages...

Страница 5: ...ions to insure that contact with energized parts is avoided when servicing Special Handling This module uses Electrostatic Sensitive Devices ESD SPECIFIC WARNINGS Disconnect power before installing di...

Страница 6: ...urant l entretien Precautions de Manutention Ce module contient des composantes sensibles aux decharges electro statiques AVERTISSEMENTS D ORDRE SP CIFIQUE Couper l alimentation avant d installer les...

Страница 7: ...l Input Mode 2 3 Internally Powered Contact Input Mode 2 3 Low Level Input Mode 2 3 MODULE DESCRIPTION 2 3 Multiplexer and Input State Circuitry 2 4 Time Base Generation 2 4 Slave Expander Bus Interfa...

Страница 8: ...NNECTIONS 5 2 SECTION 6 MAINTENANCE 6 1 INTRODUCTION 6 1 MAINTENANCE SCHEDULE 6 1 SECTION 7 REPAIR REPLACEMENT PROCEDURES 7 1 INTRODUCTION 7 1 MODULE REPAIR REPLACEMENT 7 1 SECTION 8 SUPPORT SERVICES...

Страница 9: ...gnments for NTDI01 A 2 A 5 Cable Connections for NTDI01 A 3 B 1 Input Circuit B 1 B 2 Termination Assignments for NIDI01 B 2 B 3 Configuration Summary for NIDI01 B 2 B 4 Power Supply Connections for N...

Страница 10: ...modules provide I O to the master modules This manual explains the purpose operation and maintenance of the Pulse Input Slave Module DSM It addresses handling precautions and installation procedures...

Страница 11: ...can be routed through preamplifiers so they can respond to inputs from 50 mV peak to peak to 10 V peak to peak The DSM set up information goes into an MFP using function codes Use either a configurat...

Страница 12: ...tion 2 for more information INSTRUCTION CONTENT This manual has eight sections Introduction Is an overview of the DSM Features description and specifications Description and Operation Explains the mod...

Страница 13: ...s and systems Function Code An algorithm that defines specific functions These functions link together to form the control strategy LED Light Emitting Diode the module front panel indicator that shows...

Страница 14: ...cess modules The termination module slides into a slot in the termination mounting unit TU Termination Unit Provides input output connection between plant equipment and the Infi 90 process modules The...

Страница 15: ...r frequency limit for using debounce 40Hz Mode Accuracy Totalize 0 Counts Frequency Count 1 Count Period Determination 1 Count Maximum Input Frequency 50 kHz at 50 duty cycle Timebase Accuracy 0 033 I...

Страница 16: ...e master module The master module communicates with its slave mod ule on a 12 line slave expander bus shown in Figure 2 2 Each slave on the slave expander bus has a unique address set by the slave add...

Страница 17: ...annel Frequency Operating Mode In Frequency mode the DSM counts the number of input pulses or cycles that occur in a preset period on a channel The measurement range is 0 15 millihertz to 50 kilohertz...

Страница 18: ...fiers in or out with slide switches S2 and S3 on the DSM An input voltage of 25 millivolts or more is a logic one in the module and a voltage of less than 25 millivolts is a logic 0 To select this ran...

Страница 19: ...ored for use in determining count completion Slave Expander Bus Interface The expander bus interface translates the 8 bit bidirectional expander bus into two 8 bit unidirectional internal busses one i...

Страница 20: ...set for one of six ranges The mode memory occupies one half of an 8 x 16 memory array The other half is the data valid memory The array stores the information here necessary to decide if the data val...

Страница 21: ...h the termina tion cable to edge connector P3 Connector Functions The DSM has 3 standard edge connectors along the rear of the circuit board The 12 pin connector P1 supplies the module s 5 VDC logic p...

Страница 22: ...atic discharge The Pulse Input Slave Module DSM uses electrostatic sensi tive devices Follow Steps 1 through 4 when handling 1 Keep the module in its special anti static bag until you are ready to ins...

Страница 23: ...wer slave You can use up to 20 high power slaves per master module connected to the slave expander bus The DSM can have one of 64 addresses address 0 to 63 on the slave expander bus This address uniqu...

Страница 24: ...1 0 1 36 37 38 39 1 1 1 1 0 0 0 0 0 0 0 0 1 1 1 1 0 0 1 1 0 1 0 1 8 9 10 11 0 0 0 0 0 0 0 0 1 1 1 1 0 0 0 0 0 0 1 1 0 1 0 1 40 41 42 43 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0 0 0 1 1 0 1 0 1 12 13 14 15 0 0...

Страница 25: ...termination unit used Input Jumper Settings Jumpers J 1 through J 8 set the input voltage levels and jumpers J 9 through J 16 set the DC voltage response time speed The DC inputs have two propagation...

Страница 26: ...esponse time This is useful to pre vent false triggering from switched inputs due to bounce An input that has a jumper in the debounce position will have a delay to an input transition of about 8 5 mi...

Страница 27: ...he front panel is flush with the top and bottom of the MMU frame 5 Tighten the two captive retaining screws on the module face plate To remove the module unscrew the module retain ing screws and gentl...

Страница 28: ...communicate Cable Connections The DSM uses either a NTDI01 or NIDI01 for termination See Figure 3 2 to find the cables to use with the TU TM you are using FUSING The DSM does not have any on board fus...

Страница 29: ...efer to Function Code Reference Manual I E93 900 20 for the speci fications that must be entered Most of these specifications are self explanatory When using the frequency mode there are six ranges av...

Страница 30: ...tting of S1 to match the module setup refer to the Installation Section for the pro cedures to set an address and to install a slave module OR 2 Modify the address in the module setup FC 84 specifica...

Страница 31: ...C 10 NC 5 Power Common 11 NC 6 Power Common 12 NC Table 5 2 P2 Slave Expander Bus Connections Pin P2 Signal Pin P2 Signal 1 Data 1 7 Data 7 2 Data 0 8 Data 6 3 Data 3 9 Clock 4 Data 2 10 Sync 5 Data 5...

Страница 32: ...Perform the tasks in Table 6 1 at the specified intervals Table 6 1 Maintenance Schedule Task Interval Clean and tighten each power and ground connection Every 6 months or at plant shutdown whichever...

Страница 33: ...rews are vertical and the open end of the slots face away from the module 2 Gently slide the module out of the MMU 3 Configure the replacement module switch and jumper set tings Ensure they are set th...

Страница 34: ...licable 3 Bailey instruction manual number page number and refer ence figure that identifies the part When you order standard parts from Bailey Controls use part numbers and descriptions from the Reco...

Страница 35: ...he NKTU01 cable that plugs from the termination unit to B1 on the DSM Figure A 3 shows dipshunt configuration for the possible NTDI01 applications XU7 connects the 24 VDC I O power to the preamplifier...

Страница 36: ...D C V Application Signal Type Dipshunt Configuration XU1 XU4 XU13 XU16 Dipshunt Configuration XU7 Powering an External Load Sinking an External Load Figure A 3 Dipshunt Configurations for NTDI01 Figur...

Страница 37: ...NPUTS I E96 308A A 3 Check the switch and jumper settings on the DSM and the dipshunts on the termination unit Figure A 5 shows the installation for the DSM and cables Figure A 5 Cable Connections for...

Страница 38: ...er connecting the power supply connect the field wiring to the terminal block using wire sized from number 22 AWG to number 14 AWG Route the wires so they will not interfere with the plastic front cov...

Страница 39: ...1 only needs to be made if you use the preamplifiers on the DSM input channels 1 and 2 Input circuits cannot be powered through the termi nation unit They must be externally powered If you use the pre...

Страница 40: ...09 5 CUSTOMER 24 V OUTPUT 5 V 5 V MCOM MCOM 15 V 15 V 15 V 15 V MBUS ORN WHT YEL PFI PFI MBUS I O COM I O COM L1 L2 STATUS STATUS MCOM 24 V 24 V PFI STATUS I O COM 24 V WHT BLU WHT YEL WHT ORN WHT ORN...

Страница 41: ...8756 ASIA PACIFIC 152 Beach Road Gateway East 20 04 Singapore 189721 Telephone 65 391 0800 Telefax 65 292 9011 EUROPE AFRICA MIDDLE EAST Via Puccini 2 16154 Genoa Italy Telephone 39 10 6582 943 Telefa...