FUNCTION CODE DEFINITIONS
ENHANCED ANALOG INPUT DEFINITION FUNCTION CODE (FC 216)
C - 6
I-E96-301B
®
S1
This specification contains the expander bus address of the
analog slave input module (IMASI03).
S2
This specification contains the block address of the next
enhanced analog input definition (function code 216) function
block describing one of the channels on the slave module. A
value of 2 in this specification indicates that this block is at the
end of the linked list.
S3
This specification contains the number of the input channel on
the slave described by this function block.
S4
This specification defines the input signal type of the input
from the IMASI03. Table
lists the type codes for the various
recognized input types.
For input signals which specify a defined range (for e1
to +5 V) any signals detected to fall five percent outside of that
range will be marked as bad quality with a status indication of
out-of-range.
Table C-6. FC 216 Specifications
Spec
No.
Tune
Default
Value
Data Type
Range
Min.
Max
Description
S1
No
0
INT(2)
0 to 63
Slave Address
S2
No
2
INT(2)
0 to 9998
Block Address of next enhanced
Analog Input Definition (FC216)
S3
No
1
INT(2)
Full
Slave Input Channel Number
S4
No
1
INT(1)
Full
Input Signal Type
S5
No
0
INT(1)
0 to 1
EU Conversion Type:
0 = Degrees C
1 = Degrees F
S6
Yes
0.0
REAL(3)
Full
EU Zero of input
S7
Yes
0.0
REAL(3)
Full
EU Span of input
S8
No
0.0
REAL(3)
Full
Input Signal Range Low Limit
S9
No
0.0
REAL(3)
Full
Input Signal Range High Limit
S10
No
0.0
REAL(3)
Full
Lead wire resistance (Ohms)
S11
No
16
INT(1)
16 - 24
A/D Conversion Resolution (Num-
ber of bits)
S12
No
0
INT(2)
Full
Spare parameter
S13
No
0
INT(2)
Full
Spare parameter
S14
No
0.0
REAL(3)
Full
Spare parameter
S15
No
0.0
REAL(3)
Full
Spare parameter