Page 28
4-11
Model M-2000 Mag Meter
Using the M-2000's Main Menu Programming Options
The following M-2000 programming options are available from the Main Menu:
•
Meter Setup
•
Measurements
•
Inputs/Outputs
•
Clear Totals
•
Communications
•
Advanced
•
Info/Help
•
Language Select
In the section that follows, the applicable security level for each menu option is indicated as follows:
A
S
U
Administrative
Service
User
Options that can be set at Quick Setup are indicated with:
The factory default values are shown, enclosed in brackets.
Note: Options that are listed [Factory Set] should not be changed without specific directions from authorized
Badger Meter personnel.
Meter Setup
Scale Factor
[0.0%]
S
Changing the scale factor lets you adjust the meter's accuracy without disturbing factory-set
parameters. You can tune the meter to meet changing application requirements. For example, if the
meter is under registering by 0.5 percent then set the scale factor to +0.5%. If the meter is over
registering by 0.5 percent then set the scale factor to -0.5%.
To set the Scale Factor, follow these steps from the
Meter Setup menu
:
1. Select
Scale Factor
, to open the Detector Factor display.
2. Set the Detector Factor value to the desired setting.
3. Press
[E]
, to save the new value and return to the Meter Setup menu.
Empty Pipe Detect
[Off]
S
When set to On, Empty Pipe Detect indicates to the outputs and the display that the meter is not
completely filled. When set to Off, empty pipe detect is disabled.
Enabling empty pipe detect requires a one-time calibration. Calibration is described in the Advance
Menu section under Empty Pipe Cal.
To set Empty Pipe Detect, follow these steps from the
Meter Setup menu
:
1. Select
Empty Pipe Detect
to view the Empty Pipe Detect display.
2. Position the arrow next to
On
or
Off
.
3. Press
[E]
to save the Empty Pipe Detect On or Off and return to the Meter Setup menu.