Additional programming: Industrial analog and industrial pulse
Page 9/15
AC_ILR_BA_02_1805
4.2. Analog minimum flow rate
(for models ILR750 and ILR750T)
Indicated by a “L” on the left hand side of the display, this screen allows the setting
of the flow rate that corresponds to the 4mA output:
NOTE:
The minimum flow rate value must be less that the maximum flow rate value.
• Minimum 0.0 LPM/GPM
• Maximum 100.0 LPM/GPM
• Default 0.0 LPM/GPM
NOTE:
Error checking will not allow the user to advance to the next screen.
To advance to the next programming screen, hold the
TOTAL
button for one
second.
4.3. Analog maximum flow rate
(for models ILR750 and ILR750T)
Indicated by a “H” on the left hand side of the display, this screen allows the setting
of the flow rate that corresponds to the 20mA output:
NOTE:
The maximum flow rate value must be greater than the minimum flow rate value.
• Minimum 0.0 LPM/GPM
• Maximum 100.0 LPM/GPM
• Default 30 LPM / 8 GPM
To advance to the next programming screen, hold the
TOTAL
button.
NOTE:
Error checking will not allow the user to advance to the next screen.
Figure 12: Analog maximum flow rate screen
Figure 11: Analog minimum flow rate screen