background image

12

© Copyright 2012 Badger Fire Protection

Hydrostatic Test Requirements

Hydrostatic testing is the integrity pressure testing method of a vessel utilizing a liquid compression me-
dium  Badger carbon dioxide extinguisher cylinders and hose assemblies require hydrostatic testing at 
5 year periodic intervals or any time the integrity of the vessel is questioned from any visually observed 
condition 

Visual cylinder examinations and hydrostatic testing should be performed in accordance with NFPA 10 
and D O T  CFR-49 part 180 209 recommendations 

Evidence of conditions such as exposure to fire or heat, thread damage, thread wear, corrosion, cylinder 
repairs or physical damage as detailed within NFPA 10, require the extinguisher cylinder to be removed 
from service and at the owner’s direction, disposed of in the proper manner 

Hydrostatic testing should only be performed by those persons trained in the appropriate testing proce-
dures/safeguards and having the proper testing equipment, adapters, facilities, documents and infor-
mation 

Some Badger hydrostatic test recommendations:
•  Carbon dioxide cylinder safety relief assemblies should be replaced every 5 years, when hydrostatic 

testing the cylinder  A new Badger 3 part safety assembly (P/N-24643) should be installed washer first, 
then the disc (printed side outward) and then the nut  The new safety assembly must have the proper 
amount of torque between 30 to 35 foot-pounds  Never resue safety relief components and always 
ensure the valve body seating surface is free of any damage or contamination prior to installation of 
new assemblies 

•  Extinguisher cylinders should be replaced any time the pressure vessel has been weakened due to cor-

rosion, cuts, dents, digs, etc  and be properly disposed in accordance with CGA pamphlet C-2 

•  Only water be used as the hydro-test medium and that the vessel then be flushed clean, thoroughly 

dried and visually re-examined after testing 

•  The cylinder valve assembly should be removed prior to hydrostatic testing of the cylinder. 
•  The hydrostatic test marking methods should only utilize the proper type of record labels per                    

NFPA-10 and CFR-49 stamping requirements

•  Never stamp or etch unauthorized markings onto the cylinder.
•  Any time a fire extinguisher is known to have contained agents, additives or mediums other than that 

specified on the nameplate, it should be removed from service and at the owner’s direction, disposed 
of in the proper manner 

•  No repairs to the cylinder are permitted. If such cylinder repairs are observed, the extinguisher should 

be removed from service and at the owner’s direction, disposed of in the proper manner 

•  Badger recommends cylinder valve installations be properly torqued to 150 foot punds.
•  Installation of new cylinder valve assemblies require the new fully charged cylinder weight be prop-

erly stamped on to the side of the new valve 

• Installation of siphon tubes into valve assembly should be in accordance with Badger product bulletin  
   P-224 instructions 

Hydrostatic Re-Test Data:  

Component Description   Periodic Test Interval 

   Test Pressure

Agent cylinders  3A or 3AA 

 

5 years per D O T  

 

 

 

3000 PSI

Agent hose assembly   

 

5 years (same as agent cylinder) 

 

1250 PSI

Agent manifold hose assembly  

5 years (same as agent cylinder) 

 

1250 PSI

Содержание CD50

Страница 1: ...Service Manual Self Expellling Carbon Dioxide Wheeled Fire Extinguishers Models CD50 CD50 1 CD100 CD100 1...

Страница 2: ...arts Diagram Page 14 Part Numbers and Description Page 15 Warning Failure to follow the instructions contained herein may result in property damage and or personal injury Important Notice Any time an...

Страница 3: ...r cylinders for example is amply covered in NFPA 10 and CFR 49 part 180 209 which reference procedures in CGA pamphlets C 1 C 2 and C 6A NFPA Government Printing Office Compressed Gas Association 1 Ba...

Страница 4: ...ersonnel who understand how to properly remove the associated packaging and how to properly prepare the wheeled fire extin guisher for use and fire protection service attempt to do so 1 Examine wheele...

Страница 5: ...hich might hinder the flow of agent during fire fighting 6 Operators should approach the fire from upwind to within approximately 10 15 feet of the front edge of the fire 6 Operators should approach t...

Страница 6: ...0 day intervals When circumstances require more frequent intervals may be necessary Any time an inspection reveals a discrepancy maintenance and service procedures should be performed 1 Ensure the ext...

Страница 7: ...are approved for temperatures indicated on the nameplate 2 Externally examine unit and cylinder for any signs of damage dents or corrosion that might prohibit service or dictate the need for any speci...

Страница 8: ...transportation then re install and properly secure the agent cylinder into the carriage frame Ensure the cylinder orientation correctly faces the nameplate operating instructions outward 15 Remove cy...

Страница 9: ...charge or further service of the equipment WARNING To avoid personal injury or death always ensure all pressure is properly relieved from an extinguisher prior to attempting any service repair or rech...

Страница 10: ...ually examine the cylinder valve discharge port for any signs of thread wear corrosion obstructions or accumulations of any foreign material Ensure the anti recoil device is properly installed 10 Exam...

Страница 11: ...obstructed properly secure hose assembly and using the proper service kit adaptor connect a regulated pressure source set no higher than 100 PSI to assist with clearing hose assembly 20 Ensure the dis...

Страница 12: ...ny damage or contamination prior to installation of new assemblies Extinguisher cylinders should be replaced any time the pressure vessel has been weakened due to cor rosion cuts dents digs etc and be...

Страница 13: ...der outside tolerance De pressurize and recharge Operating instructions missing or illegible Replace Agent cylinder burned or repaired Replace Agent cylinder damaged or corroded Inspect hydrostatic re...

Страница 14: ...14 Copyright 2012 Badger Fire Protection Extinguisher Parts Diagram Badger Carbon Dioxide Wheeled Extinguishers CD50 CD50 1 CD100 and CD100 1...

Страница 15: ...ain 9 22776 chain drive pin 10 24643 safety relief assembly nut disc and washer 11 22776 siphon tube assembly 12 13735 replacement non flammable gas label 13 22785 replacemtn UN 1013 label 14 22873 Re...

Страница 16: ...Badger Fire Protection 944 Glenwood Station Lane Suite 303 Charlottesville Virginia 22911 www badgerfire com Phone 1 800 964 3200 Manual BP84A P N 24645 Rev 07 12 Copyright 2012...

Отзывы: