MGS-350 Manual
32
6509-9000 Rev 1
4.4. Calibration: Gas Method
This is the adjustment of the gas detector’s accuracy using calibration
gas. Bacharach offers a calibration kit that consists of a Calibration gas
cylinder and a flow regulation valve with flexible non-absorbent tubing
and vented calibration hood.
In many cases this option may be expensive because of the cost of
visiting a site and the cost of the calibration gas and possibly excess
delivery charges as it is classified as a hazardous substance.
The MGS-350 consists of a motherboard PCB and a sensor board PCB.
There are four sensor board versions: SC, EC, CAT and IR, but the
motherboard is the same for all models.
Calculating Calibration Voltage
Calibration is done on a 0-10V scale, however the alarm relay setting
pots work on a 0-5V scale.
Sensor outputs are linear. As long as you have a gas cylinder of known
concentration you can calibrate to any desired range.
Figure 11. Example Sensor Board and Motherboard