MGS-350 Manual
22
6509-9000 Rev 1
Item
Description
JP2
Relay 2 delayed response time (Default: 0 minutes)
JP3/JP4
Jumpers to set normally open/closed for relay 1
JP5
Jumper to set normally open/closed for relay 2
JP7
Jumper to set latching for relay 2 (Default Automatic).
JP8
Jumper to set latching for relay 1 (Default Automatic).
RV1
Alarm Threshold level set by RV1 and can be set by
putting a meter between TP0 (negative) and TP2
(positive) and adjusting RV1 (scale is 0 to 5V e.g. 2.5V
is 50% of calibrated range) to the setpoint at which the
relay activates. Check rating plate on the side of the
MGS-350 for alarm relay settings.
TP0
TP2
RV2
Alarm Threshold level set by RV2 and can be set by
putting a meter between TP0 (negative) and TP3
(positive) and adjusting RV2 (scale is 0 to 5V e.g. 2.5V
is 50% of calibrated range) to the setpoint at which the
relay activates. Check rating plate on the side of the
MGS-350 for alarm relay settings.
TP0
TP3
NOTE:
After adjusting relay settings or modifying jumpers,
the unit must be powered off and on again to store the new
settings.
2.8. Connecting to an MGS Controller
Multiple MGS-350s may connect to a 2- or 6-channel MGS Controller.
For details on wiring and installation, refer to the MGS Controller Manual
(P/N 6709-9000).
NOTE:
The MGS-350 has an addressing capability and a
RS-485 interface for connection to higher-level controller
systems.
Содержание MGS-350
Страница 10: ...MGS 350 Manual 10 6509 9000 Rev 1 Figure 2 MGS 350 IP66 Housing with Splash Guard...
Страница 11: ...MGS 350 Manual 6509 9000 Rev 1 11 Figure 3 IP66 Splashguard M42 x 1 5 Thread Figure 4 IP66 Duct Mount Housing...
Страница 12: ...MGS 350 Manual 12 6509 9000 Rev 1 Figure 5 Exd Housing Units mm...
Страница 42: ...MGS 350 Manual 42 6509 9000 Rev 1...
Страница 43: ...MGS 350 Manual 6509 9000 Rev 1 43...