1:  OPERATING AREA AND CONDITIONS

The Bacharach MGS-250 is an instrument for the 

continuous monitoring of refrigerant gases. 
The instrument is powered by 24V AC or DC.  The 

output signal can be selected as either voltage or 

current.  The on-board relay can be used to switch 

alarm devices.

2:  SAFETY INSTRUCTIONS

USER MANUAL: 

 Before using this equipment, 

carefully read and strictly follow the User Manual 

(part number

 6490-9000)

.  The user must fully 

understand and strictly observe the instructions.  

Use the equipment only for the purposes listed and 

under the conditions specified in those documents.

CODE COMPLIANCE:  

Comply with all local and 

national laws, rules and regulations associated with 

this equipment. 

GENUINE PARTS: 

 Use only genuine Bacharach spare 

parts and accessories, otherwise proper functioning 

of the equipment may be impaired.

TECHNICIAN USE ONLY: 

This unit must be installed 

by a suitably qualified technician who will install this 

unit in accordance with these instructions and the 

standards in their particular industry/country. Opera

-

tors of the unit should be aware of the regulations 

and standards in their industry/country for the 

operation of this unit. These notes are only intended 

as a guide and the manufacturer bears no responsi

-

bility for the installation or operation of this unit.
Failure to install and operate the unit in accordance 

with these instructions and with industry guidelines 

may cause serious injury including death and the 

manufacturer will not be held responsible in this 

regard.

SAFE MOUNTING: 

This monitor must be connected 

by a marked, suitably located and easily reached 

switch or circuit-breaker as means of disconnection.

WARNING:  

Strictly follow the 

instructions in the Gas Detector 

Manual (part number 6490-9000) 

available at www.MyBacharach.com. 

CAUTION: 

 DO NOT MOUNT the 

MGS-250 in an area that may 

contain flammable liquids or 

vapors. Operation of electrical 

equipment in such an area consti

-

tutes a safety hazard.

GAS DETECTOR

INSTALLATION GUIDE

3:  SPECIFICATIONS

To open the housing as received use a flat blade 

screwdriver and depress the top latch. While push

-

ing the latch, grasp the back edge of the housing 

near the latch and pull the back away.

4:  MOUNTING

Sensor 

Housing

6.3 oz

4.0” x 5.5” x 1.5”

180 g

102 x 140 x 37 mm

Weight

and

Dimensions

Temperature

Rating

-22° to 104° F

-30° to 40° C

Enclosure

ABS plastic; UL flammability

rating of 94V-0

Approvals

CE, UL/CSA/IEC/EN 61010-1

NOTE: 

When installed in areas that may be

subjected to water spray, the optional splash

guard (P/N: 6900-0001) should be used in

conjunction with the MGS-250.  Weight and 

dimensions (above) do not include optional

splash guard.

When mounted, the housing is simply opened by 

pressing the top latch with a suitable screwdriver or 

other flat blade.  With the top latch depressed pull 

the housing apart by grasping the sides and pulling 

straight out.  With the housing separated the 

mounting base with terminal blocks will be visible.

IMPORTANT: 

Do not apply caulking or 

other material around the gas detector 

base.  The gas detector relies on air 

exchange through the spaces between the 

base and the gas detector housing.  Do not 

obstruct the small gap around the housing 

and the base with any material.

ACCESSIBILITY: 

 The mounting location of the moni

-

tor should allow it to be easily accessible for visual 

monitoring and servicing.

VIBRATION FREE LOCATION:  

Do NOT mount the 

MGS-250 directly to vibrating machinery as the 

vibrations may degrade the gas detector’s perfor

-

mance.

PLACEMENT GUIDELINES:  

The MGS-250 should be 

installed plumb and level and securely fastened to a 

rigid mounting surface. 

WATER SPRAY:  

When installed in areas that may be 

subjected to water spray, the optional splash guard 

(P/N: 6900-0001) should be used in conjunction with 

the MGS-250.

ENVIRONMENTAL CONSIDERATIONS: 

 Carefully 

consider the full range of environmental conditions 

to which the instruments will be exposed.

TARGET GAS CONSIDERATIONS:  

The physical data of 

the gas or vapor to be detected must be observed.

APPLICATION CONSIDERATIONS:  

The specifics of 

the application (for example, possible leaks, air 

movement/draft, etc.) must be observed.

ACCESSIBILITY CONSIDERATIONS:  

The degree of 

accessibility required for maintenance purposes 

must be granted.

ACCESSORY CONSIDERATIONS: 

 The types of 

optional and accessory equipment that will be used 

with the system must be kept in mind.

ELECTRONIC CONSIDERATIONS: 

The system contains 

sensitive electronic components that can be easily 

damaged. Do not touch nor disturb any of these 

components.
Mount the MGS-250 according to the above consid

-

erations, product dimensions (see Section 3), maxi

-

mum wiring lengths (see Section 5), and the corre

-

sponding mounting dimensions shown in the illustra

-

tions that follow.

STEP 1: 

  Open the housing.

STEP 2: 

  Position the base to the pre-determined 

(acceptable) mounting location.  Use the gas detec

-

tor base to mark the mounting locations as needed.  

The hole pattern on the back plate is sized to mount 

the gas detector onto various electrical junction 

boxes.  The other holes may be used as needed to 

mount the gas detector to other structures, or onto 

a wall. 

STEP 3 - FOR WALL MOUNT: 

  Attach the MGS-250 

base to the mounting surface using two #6 screws 

(provided) through two of the mounting holes, being 

careful not to over-tighten the screws.

STEP 3 - FOR JUNCTION BOX MOUNT: 

  Attach the 

MGS-250 base to the junction box (using mounting 

hardware provided with your junction box) through 

the two junction box holes.

STEP 4: 

  Unless you are ready to wire the device, 

carefully snap the cover onto the base unit.

P/N: 6490-9004

Revision 0

January 25, 2016

4:  MOUNTING (CONTINUED)

4:  MOUNTING (CONTINUED)

Flat Surface

Mounting Holes

(6 Places)

NOTE:

  

Use #6

screw or smaller for

wall mounting.

Junction Box

Mounting

Holes (2 Places)

Cable Gland

(Optional) or

Blanking Plug

(Not Shown)

Cable Gland

(Installed)

DO NO

T

 apply c

aulking or sealan

t on or

ar

ound the MGS

-250 or its base.