Installation Guide 

 

Bacharach HGM300 to LonWorks FT-10 

Communications Adapter 

 

 
 

Introduction 

 
The Bacharach HGM300 to LonWorks Communications Adapter enables an HGM300 
Refrigerant Monitor to communicate with a LonWorks FT-10 Free Topology network.  
Zone PPM readings, flow status, refrigerant selections, and HGM internal health may be 
viewed over LonWorks.  Each HGM zone supports three levels of alarming (Leak, Spill, 
Evacuate) and each alarm threshold can be set over LonWorks. 
 
The LonWorks Communications Adapter can be used in conjunction with the RDM800 
remote display if desired.  Wiring details and operation limitations when using the 
RDM800 will be discussed later in this document. 
 

Caution 
 

The adapter is powered from the 120V Auxiliary Power connection on the HGM power 
supply board.  When the HGM is powered up, 120V is present on the lower left corner of 
the adapter within the area shown on the board silkscreen.  Keep fingers away from this 
area when the HGM is powered!! 
 

Adapter Installation Inside HGM300 

 
The communications adapter board will normally be installed in the HGM300 at the 
factory.  It can, however, be field installed by following the instructions below. 
 
The following installation materials are needed for field installation of the adapter: 
 
(5) 6-32 x ¼” screws (standard finish) 
(5) 6-32 x ½” threaded standoffs 
(5) 6-32 x ¼” decorative black anodized screws (standard finish OK, black looks nicer) 
 
The adapter board mounts on the rear of the HGM300 door.  Position the adapter board 
so as not to interfere with the HGM internal components when the door is shut.  Mark 
(Figure 1) and drill the board’s four corner holes and center hole in the door.  Install the 
five standoffs on the rear side of the door using the five black decorative screws on the  
 
 

Содержание LonWorks FT-10

Страница 1: ...n on the HGM power supply board When the HGM is powered up 120V is present on the lower left corner of the adapter within the area shown on the board silkscreen Keep fingers away from this area when t...

Страница 2: ...g from the HGM300 s 120V Auxiliary Power terminal block to the adapter board s POWER terminal block Use UL approved wire Wire polarity does not matter If an RDM800 remote display is NOT used with the...

Страница 3: ...to Figure 3 for wiring details Note that when the RDM800 is used TWO RS 485 cables must be run between the HGM300 and RDM800 so plan accordingly In either case be sure to set the HGM300 s internal Ter...

Страница 4: ...4 of 18...

Страница 5: ...ble HGM address A5 A6 A7 A8 0 Off Off Off Off 1 Off Off Off On 2 Off Off On Off 3 Off Off On On 4 Off On Off Off 5 Off On Off On 6 Off On On Off 7 Off On On On 8 On Off Off Off 9 On Off Off On 10 On O...

Страница 6: ...6 of 18...

Страница 7: ...ker and possibly others will accept User Resource files A subset of the information in these files is permanently stored in the adapter itself and may be queried over the network once the network mana...

Страница 8: ...s alarm outputs until LonWorks has acknowledged the alarms using network variables nviHgmAlmAck or nviHgmAlmAckSw discussed below Once LonWorks has acknowledged the alarms the HGM will clear its alarm...

Страница 9: ...object to be reported through nvoStatus works identically to RQ_UPDATE_STATUS 2 RQ_UPDATE_STATUS value 2 Requests the status of the object specified in the object ID field If sent to the Object Node...

Страница 10: ...out a status update on each expiration of that amount of time It rotates through the objects on the node in round robin fashion when timed updates are sent in this manner Any zone which is disabled o...

Страница 11: ...the zone status and the refrigerant type being sensed Possible Zone Status values ZONE NORMAL No alarms no faults HGM in normal operating mode LEAK ALARM Leak alarm active for this zone SPILL ALARM S...

Страница 12: ...al processors HGM WARMING UP HGM must go thru warmup cycle after powerup before measuring ZONE DISABLED This zone has tubing length set 0 disabled NOT_INSTALLED This zone does not have hardware instal...

Страница 13: ...full scale value may display as 200 or 100 0 Network output variable nvoHgmFaults bit field structure reports various faults within the HGM300 or the LonWorks adapter It contains 14 faults 1 bit fiel...

Страница 14: ...2 Unused bit 1 Unused bit 0 least significant bit Network output variable nvoZoneSampling shows which zone is currently being sampled by the HGM It is a number 1 16 Note that if fewer than 16 zones a...

Страница 15: ...ies which zone alarm the operator wishes to acknowledge A value of 1 16 acknowledges the alarm for a single specified zone A value of 0 is a global acknowledge for all zones in alarm Network input var...

Страница 16: ...esentation software the full scale value may show as either 200 or 100 0 Network output variable nvoHgmLeakAlert reports whenever any Leak alarm is generated by the HGM It is of type SNVT_switch It is...

Страница 17: ...ill resume If the operator leaves the RDM800 in some screen other than SYSTEM or ZONE VIEW for an extended period of time 10 minutes default the RDM800 times out and automatically returns to either th...

Страница 18: ...get the changes from LonWorks and pass the new thresholds down to the HGM The HGM then takes a certain amount of time to process the changes and store them in its nonvolatile memory Then since the HGM...