GDA-1600 16-Channel Controller
Instruction 5700-9001
48
energized by low battery conditions. The actual battery voltage of each GDX-350
RF may be seen in the
INPUT DATA FROM
screen.
•
Calibrations
performed at the GDX-350 RF force a transmission of 75 counts
(negative 15.62%) which may be indicated on the GDA-1600’s LCD readout by
In Cal
by using the “Marker Menu” described in section 2.2.4b. Alarms are
inhibited while the “Marker Value” of -15.62% is activated.
Figure 8
.4
8.3.2 Wireless Modbus Slave Mode
Wireless MODBUS
allows one or many GDA-1600s to function as wireless Modbus
slaves
by connecting their RS-485 Modbus
slave
The entire GDA-1600 Modbus database, including registers and supported Function
Codes, is documented in section 5.1.
ports to a radio modem. These wireless
networks require a Modbus
master
such as a DCS, HMI or another GDA-1600 also
equipped with a radio modem. One transceiver must be designated as Server and all
others as Clients. No special configuration is required by the
master
or
slave
since this is
a standard Modbus network. However, radios must have the same
Hop Channel
and
System ID
settings to communicate. Radio modules may only be configured when
connected to the GDA-1600’s
master
port. If it is necessary to modify
Hop Channel
and
System ID
settings, the radio module may be temporarily connected to the GDA-
1600’s master port for configuration then moved back to the
slave
port for operation.
8.4 Wireless Modbus Master Mode
GDA-1600 applications as a “Wireless Modbus master” are similar to the “Wireless
Receiver” mode described in section 8.3 (on page 47) and wiring to the radio modem is
identical. The radio setup menus described in section 8.2 may also be used for
configuring hop channel and system ID settings. The difference is each channel’s
INPUT DATA FROM
menu must be configured with the correct
MODBUS
values to
match the slave device instead of
Wireless RF900.
Wired and wireless inputs may be
mixed between the GDA-1600’s sixteen channels so it is also possible to accept wired
signals from analog input option PCBs described in section 4.2.
This is a popular application when the Modbus slave is another remote GDA-1600 or our
GDA-400 controller available with built in radio modem compatible with the GDA-1600
Содержание GDA-1600
Страница 12: ...GDA 1600 16 Channel Controller Instruction 5700 9001 12 Figure 3 1 Channel Configuration Menus ...
Страница 21: ...Instruction 5700 9001 GDA 1600 16 Channel Controller 21 Figure 3 10 Configuration Menus ...
Страница 28: ...GDA 1600 16 Channel Controller Instruction 5700 9001 28 Figure 4 2 Main PCB ...
Страница 36: ...GDA 1600 16 Channel Controller Instruction 5700 9001 36 Figure 4 7 Analog Output Board ...
Страница 38: ...GDA 1600 16 Channel Controller Instruction 5700 9001 38 Figure 5 2 System Diagnostic Options ...
Страница 53: ...Instruction 5700 9001 GDA 1600 16 Channel Controller 53 ...