WAVE-PIR-120/277-N
Best: 320 sq.ft.
The coverage range of the sensor switch is specified and illustrated
Control Panel Cover
LED Indicator
OFF VAC VAC
TIME
TEST
10
20
30
Min
Min
Min
RANGE
LIGHT
3
3
2
Mounting Yoke
Fresnel Lens
OFF VAC VAC
Figure 4
4
1
2
4
1
- 01-
-03-
-02-
DESCRIPTION
P
art Number: 97332
VACANCY SENSOR
SPECIFICATIONS
SWITCH
INSTALLATION
Turn off the circuit breaker before installation;
WARNING:
Do not exceed electrical ratings.
to Hot wire, Red lead to Load wire, White lead to Neutral wire, and
2. Gently position wires in wall box, attach sensor switch to the box.
3. Mount device “TOP”up.
4. Restore power at circuit breaker or fuse, wait
6. Locate the adjustment knobs on the control panel to perform test
ADJUSTMENT
INSTALLATION INSTRUCTIONS
In door use only;
Wiring Diagram:
Figure 2
VAC
Mode
OFF
VAC
Description
Circuit is permanently opened.
Position
Left
Center
Right
Vacancy Mode: Manual On only,
Automatic Off after set time delay.
Function of the push-button
Manually toggles
None
Manually toggles
1. Connect lead wires as WIRING DIAGRAM (see Figure 2): Black lead
the light to turn off eventhough someone is still in the detection area.
The passive infrared sensors work by detecting the difference between
heat emitted from the human body in motion and the background space.
in Figure 1. Large objects and some transparent barriers like glass
windows will obstruct the sensors' view and prevent detection, causing
Coverage Area
Band switch prescription.
If no motion is detected for the set time delay, the load turned off
automatically. The sensor switch has one relay (equal to single pole
switch), also includes Ambient Light Level Sensor.
5. Remove the small cover plate. (Illustrated as Figure 3. )
7. Replace the small cover plate after testing and adjustment.
8. Attach the wallplate.
Figure 3
(switched off)
On / Off the load.
On/Off the load.
and adjustment.(Illustrated as Figure 3. )
Default position: 15 Seconds (Test mode)
Adjustable: from 15 Seconds to 30 Minutes (clockwise)
Default position: Center at 65%
Adjustable: 30% (Position 1) to 100% (Position 4)
Note: Turn toward right for greater room space.
Turn toward left to avoid false alert in smaller room and near the
door way or heat source.
Default position: Daylight (100% at position 4)
Adjustable: Daylight to 30Lux (Counter clockwise)
Note: to avoid wasting energy by turn-on the light under daylight.
Time Delay knob
Sensor Sensitivity Range Knob
Ambient Light Level Knob
Green lead to Ground wire.
Figure 1
one
minute.
(Push Button)
Regular: 800 sq.ft.
Maximum: 1200 sq.ft.
40'
Top View
20'
10'
20'
10'
20'
5'
4'
Incandescent .............................................................................800W
Time Delay...........................................................…… 15Sec to 30Mins
Light Level.................................................................... 30 Lux--Daylight
Fluorescent/Ballast
/LED
...............800VA@120VAC /1600VA@277VAC
Operation Temperature...................................................... 32 F--131 F
Voltage ....................................................................120/277VAC, 60Hz
Motor ...................................................................................…… 1/4HP
NOTE: DO NOT connect RED & WHITE wires on device together! It
may cause short circuit!
Neutral
White
Hot
Black
Ground
Green
Load
Red
Load
Neutral
White
Vacancy Mode: Manual On only,
Automatic Off after set time delay.