WAVE-PIR-120/277-N

Best: 320 sq.ft.

The coverage range of the sensor switch is specified and illustrated 

Control Panel Cover

LED Indicator

OFF  VAC  VAC

TIME

TEST

10

20

30

Min

Min

Min

RANGE

LIGHT

3

3

2

Mounting Yoke

Fresnel Lens

OFF  VAC  VAC

Figure 4

4

1

2

4

1

- 01-

-03-

-02-

DESCRIPTION

P

art Number: 97332

VACANCY SENSOR 

SPECIFICATIONS

SWITCH

 

INSTALLATION

 Turn off the circuit breaker before installation;  

WARNING:

Do not exceed electrical ratings.

to Hot wire, Red lead to Load wire, White lead to Neutral wire, and

2. Gently position wires in wall box, attach sensor switch to the box.

3. Mount device “TOP”up.

4. Restore power at circuit breaker or fuse, wait

6. Locate the adjustment knobs on the control panel to perform test

ADJUSTMENT

INSTALLATION INSTRUCTIONS

In door use only;

Wiring Diagram:

Figure 2

VAC 

Mode

OFF

VAC 

Description

Circuit is permanently opened.

Position

Left

Center

Right

Vacancy Mode: Manual On only, 

Automatic Off after set time delay.

Function of  the push-button

Manually toggles 

None

Manually toggles 

1. Connect lead wires as WIRING DIAGRAM (see Figure 2): Black lead

the light to turn off  eventhough someone is still in the detection area.

The passive infrared sensors work by detecting the difference between

heat emitted from the human body in motion and the background space.

in Figure 1. Large objects and some transparent barriers like glass 

windows will obstruct the sensors' view and prevent detection, causing

Coverage Area

Band switch prescription.

If no motion is detected for the set time delay, the load turned off 

automatically. The sensor switch has one relay (equal to single pole 

switch), also includes Ambient Light Level Sensor. 

5. Remove the small cover plate.  (Illustrated as Figure 3. )

7. Replace the small cover plate after testing and adjustment.

8. Attach the wallplate.

Figure 3

(switched off)

On / Off the load.

On/Off the load.

and adjustment.(Illustrated as Figure 3. )

Default position: 15 Seconds (Test mode)

Adjustable: from 15 Seconds to 30 Minutes (clockwise)

Default position: Center at 65%

Adjustable: 30% (Position 1) to 100% (Position 4)

Note: Turn toward right for greater room space.

      Turn toward left to avoid false alert in smaller room and near the

door way or heat source.  

Default position: Daylight (100% at position 4)

Adjustable: Daylight to 30Lux (Counter clockwise) 

Note: to avoid wasting energy by turn-on the light under daylight.

Time Delay knob

Sensor Sensitivity Range Knob

Ambient Light Level Knob

Green lead to Ground wire.

Figure 1

 one

 minute.

(Push Button)

Regular: 800 sq.ft.

Maximum: 1200 sq.ft.

40'

Top View

20'

10'

20'

10'

20'

5'
4'

Incandescent .............................................................................800W

Time Delay...........................................................……  15Sec to 30Mins

Light Level....................................................................  30 Lux--Daylight

Fluorescent/Ballast

/LED

...............800VA@120VAC /1600VA@277VAC

      

Operation Temperature...................................................... 32 F--131 F

Voltage ....................................................................120/277VAC, 60Hz

Motor  ...................................................................................…… 1/4HP

NOTE: DO NOT connect  RED & WHITE wires on device together! It

may cause short circuit! 

Neutral

White

Hot

Black

Ground

Green

Load

Red

Load

Neutral

White

Vacancy Mode: Manual On only, 

Automatic Off after set time delay.