Installation and Operating Instruction for 

B.E.G.

 Controls - Occupancy sensor MINI-P-PP-DIM-GH-W-FC

MINI-P-PP-DIM-GH-W-FC

Controls

B.E.G.

  1. Product information

• 

MINI primary sensor for use with PP-DIM-J pow-

er pack or proprietary low voltage system

• 

Designed for wet and high-humidity locations 

and high-bay applications

• 

Up to 4 Secondary sensors may be connected 

with a primary sensor to increase detection 

coverage.

• 

Spring clips for quick and easy installation in 

suspended ceilings and light fixtures

• 

5-year limited warranty

• 

Masking blinds included

• 

All programmable features can be adjusted via 

B.E.G. Controls smartphone IR-Adapter and 

Android or iOS app.

• 

ROHS compliant

• 

Photocell included as a standard feature

2. Operation with power pack  

 PP-DIM-J

Automatic Mode

In automatic mode the power relay closes when mo-

tion is detected, then the power pack automatically 

adjusts the dimming load to the programmed level 

set by the installer.
The dimming load turns-off when motion is no longer 

detected and the follow-up time elapses. Using the 

momentary switch option, wired to the power pack, 

the occupant can toggle the lighting load on/off 

by pressing and releasing the switch. Pressing and 

holding the switch will either increase or decrease 

the light level. The selected occupant level will 

remain until no motion is detected and the follow-

up time elapses. When motion is detected again 

the power pack will adjust the dimming load to the 

programmed level set by the installer.

Orientation Mode

This mode includes two configurations. Timed and 

Permanent.
In the timed orientation mode, once motion is no longer 

detected and the follow-up time elapses, the power 

pack decreases the dimming load to a pre-adjusted 

level for a selectable time period (between 30 seconds 

and 30 minutes), then the load is turned-off.  
In the permanent orientation mode, the power pack 

does not switch the load-off completely. When motion 

is no longer detected and the follow-up time elapses, 

the dimming load is decreased to a preset level and 

stays at that level until motion is detected again or the 

momentary switch is pressed.
In either mode, should the ambient light level surpass 

the maximum daylight parameter (100 fc), the load 

dim to a 1% level. If the ambient light remains at 

this level for five minutes the load will turn-off.  If the 

ambient light level is close to the minimum daylight 

parameter (2 fc), the load will turn-on.

Semiautomatic Mode

In the semiautomatic mode the power relay only closes 

when occupant presses momentary switch, then power 

pack automatically adjusts the dimming load to the 

programmed level set by the installer.  The dimming 

load turns-off when motion is no longer detected and 

the follow-up time elapses.  Using the momentary switch 

option, the occupant can toggle the lighting load on/

off by pressing and releasing the switch.  Pressing and 

holding the switch will either increase or decrease the 

light level.  The selected occupant level will remain until 

no motion is detected and the follow-up time elapses.  

When occupant presses switch again, the power pack 

will adjust the dimming load to the programmed level 

set by the installer. 

 

3. Safety information

!

  

 Work should be carried out by qualified pro-

fessionals or by instructed persons under the 

direction and supervision of qualified skilled 

electrical personnel in accordance with electri-

cal regulations.

!

   The device is not to be used to isolate other 

equipment from the mains supply!

4.   Mounting

Select sensor(s) mounting 

location based on room 

dimensions and sensor 

coverage pattern. Avoid 

placing sensor(s) less 

than four feet away from 

heat and/or ventilation 

sources. Avoid placing 

sensor(s) where view will 

be directed outside of in-

tended controlled space, 

this to prevent outside sources from activating sensor(s).

A circular opening 1.3 in/34 mm in diameter must be 

made in the ceiling.

Having connected the cables in accwinordance with 

the national and local electrical codes, connect the 

sensor to the power pack using the RJ12 connector. 

Pass sensor’s RJ12 connector through ceiling opening. 

Next, squeeze spring clips through ceiling opening. 

Sensor should clip securely into place.

(See Figure)

!

    

When using primary and secondary devices, 

please mount the primary device at the place 

with the least amount of natural light.

5.  Position LEDs

1

LED 1 green/red

6. Self test cycle/Startup behavior

When power is first applied, the sensor enters an 

initial 60 second self-test cycle. During this time the 

device does not respond to movement and stays on.

7. Range 

20ft / 6

m

30 ft / 

9 m

1

1

Walking across

8. Exclude sources of interference

 

To prevent false activation from external heat-emitting 

sources, use blinds to mask sensor viewing angle.

9. Description / Part No. / Accessory

Description

Part No.

MINI-P-PP-DIM-GH-W-FC

97198

MINI-S-PP-GH-W-FC

97197

Remote control:

via B.E.G. Controls IR-Adapter

92726

Power pack PP-DIM-J

97017

The required app for smartphones can be down-

loaded from the App Store for iOS smartphones and 

Google Play Store for Android smartphones. 

The manual for the B.E.G. Controls App can be 

downloaded from www.begcontrols.com

Note:

  Remote only works with primary MINI-P-PP-

DIM-GH-W-FC sensor.

Note:

  

Maximum distance between sensor and 

remote - 24 ft / 7.3 m

10. Technical data

Operating voltage:

      24 V DC 

Ambient temperature:

  -13°F-122°F/-25°C to +50°C

Protection:

  Suitable for outdoor use and wet  

locations.

Factory settings: 

50 fc/500 Lux, 10 min.

Recommended height  

for mounting:

  

30 ft / 9 m

Range of coverage Ø:

  walking across 19.7 ft /6 m

Area of coverage:

  

360°

DIM output:

  

0-10 V DC, up to 50 EB

Following settings can only be changed using the 

B.E.G. Controls IR-Adapter for smartphones and app. 

Brightness set value:

  2 - 100 fc/20 - 1000 Lux 

Follow-up time:

 

 Load: 30 sec. - 30 min.

Sensitivity: 

MIN-LOW-MID-HIGH-MAX

Dimensions:

 

 H 1.6 in x Ø 1.77 in  

H 41 x Ø 45 mm

Technical data MINI-Secondary

Power supply:

   

24 V DC

Pulse output:

   

Digital output

Pulse duration:

   

1sec. ON, 9 sec. OFF

    

11. Manual switching

!

  

See manual of the power pack PP-DIM-J!

 

 34 mm

≤1.3 in

9118_MINI-P-PP-DIM-GH-W-FC_130916.indd   1

02.03.2017   12:40:45

Содержание MINI-P-PP-DIM-GH-W-FC

Страница 1: ...he selected occupant level will remain until no motion is detected and the follow up time elapses When occupant presses switch again the power pack will adjust the dimming load to the programmed level set by the installer 3 Safety information Work should be carried out by qualified pro fessionals or by instructed persons under the direction and supervision of qualified skilled electrical personnel...

Страница 2: ...ngs lock is activated the detector can be released again as follows Disconnect and reconnect sensor from power pack Let sensor initialize for about 31 to 59 seconds Disconnect sensor from power pack Connect sensor back to power pack and wait for the sensor to go through self testing Press the unlock button Pressing the RESET button on the remote control in programming open mode will delete all of ...

Страница 3: ...check that the Smartphone s loudness level is maximum in order to ensure a correct operation 2 Procedure to use the remote control app Start page Help To access the device selection page click on the three white horizontal lines in the upper left corner or swipe from left to right Device or remote control selection Select Remote controls Select IR MINI P Functions Device section 1 Open unlock the ...

Страница 4: ...ters at once You may want to apply the same parameter settings to more than just one MINI Primary sensor in this case you can use the Activate Deactivate function to select multiple commands The Send highlighted commands button will then send all selected parameters Please note that this is only applicable for open state functions The app will always send the Open de vice command before sending al...

Отзывы: