B.E.G. LUXOMAT Скачать руководство пользователя страница 1

Installation and operating instructions

LUXOMAT

®

KNXnet/IP Interface Multicontrol

GB

 1. General use 

 

The KNXnet/IP Interface Multicontrol includes all the modules 

required to implement time switching functions, trigger condi-

tions for defined events, event handling, logic functions and 

the function of a real-time clock.

The following are available:

- Weekly switching programs (100 time switch entries)
- Event trigger / threshold switch (30 triggers)
- Event processing / scenes (200 events)
- Logic functions (30 logic functions)
- Real-time clock with battery backup
- Tunnel link to bus for visualisation
- Automatic time synchronisation via UDP time server
- Automatic adjustment to daylight-saving time
- IP address assignment via DHCP

In the device, up to 80 objects are defined with free data 

type assignment from the following options:

- 1 bit (EIS 1)
- 1 byte without sign bit (EIS 14)
- 1 byte with sign bit (EIS 14)
- 2 bytes without sign bit (EIS 10)
- 2 bytes with sign bit (EIS 10)
- 2 bytes floating (EIS 5)
- 4 bytes without sign bit (EIS 11)
- 4 bytes with sign bit (EIS 11)
- 4 bytes floating (EIS 9)

7.   Location and function of indication and control 

elements

The device connections, as well as the learn button and pro-

gramming LED that are required during EIB startup, can only 

be accessed in the distributor when the cover is removed. 

The pushbuttons (Move, Prg/Set, ESC) and the 2 - line display 

can be operated when the distributor cover is closed.

A1:

    24 V bus terminal

A2: 

   KNX bus terminal

A3:

  Ethernet RJ45 socket

A4:

  KNX programming LED

A5:

  KNX learn button

A6:

  Display 2 x 12 characters

A7:

  Move button

A8:

  Prg/Set button

A9: 

ESC button

A10:

  Ethernet Link LED

A11: 

Ethernet Activity LED

A12:

  Battery compartment

6. Technical data

Power supplies

•  24 V AC/DC; input range 12 .. 30 V AC/DC

•  Additionally via EIB/KNX bus

Control elements

•   Learn button for switching between standard and 

addressing   mode

•   3 x pushbuttons (Move, Prg/Set, ESC) on the front for 

setting the device (time and date) and indication of 

the IP and MAC address

Indication elements

•  Red LED for indicating standard/addressing mode

•  Green LK LED for indicating the Ethernet link

•   Green LA LED for indicating communication on the 

Ethernet link

•   LCD with 2 lines of 12 characters for indicating the 

time and date

Connections

•  Bus line: EIB/KNX bus terminal (black/red)

•  Power supply: Bus terminal (yellow/white)

•  Ethernet 10 Mbps: RJ45 socket

Mechanical data

•  Casing: Plastic LEXAN UL-94-V0 

 

•  Dimen sions for REG casing 4 div.: 

Width:  70 mm 

Height:   55 mm 

Length: 86 mm

•  Weight: 150 g

•  Installation: On standard 35 mm DIN rail

Electrical safety

•  Pollution degree: 

2

•  Degree of protection (according to EN 60529): IP20

•  Protection class (according to IEC 1140):  

I

•  Surge voltage category:  

III

•  Bus: Safety extra-low voltage SELV 24 V DC

EMC requirements

Meets EN 50081-1 and EN 50082-2,

EN 50090-2-2

Ambient conditions

•  Resistance to extreme climates: EN 50090-2-2,

•  Ambient conditions during operationb: 0°C to +45°C

•  Storage temperature: -25°C to +70°C

•  Relative humidity (no condensation): 5 % to 93 %

Approval

EIB/KNX registered

CE marking

 In accordance with EMC directive (residential and functional 

building), low-voltage directive

 2. Device types and accessories 

 

At present, the following device types are available from the 

Interface product group:

KNXnet/IP Interface Multicontrol 

Part number: 90124

KNXnet/IP Interface 

 

Part number: 90125

KNXnet/IP Interface Web 

Part number: 90126

3. Scope of supply 

 

The KNXnet/IP Interface Multicontrol is supplied as standard 

with the following individual components:

•  Complete device including battery with EIB bus terminal 

(black/red) and 24 V supply bus terminal (yellow/white) 

inserted

• Operating and installation instructions

4. Application programs 

 

At present, the following application programs are available: 

KNXInterface-90124, for function of the application program 

see application program description

A4

A1

A3

A7

A8

A9

A6

A10

A11

A12

A5

A2

All defined objects can be used by all available modules. 

This means that up to 80 objects can be selected for time 

switching functions, as inputs for logic functions, as trigger 

objects or as outputs for the event programs.

46

60

86

70

55

46

5. Installation notes

•   The device should only be installed and started up by an 

approved electrical engineer.

•   Observe the applicable safety and accident prevention 

regulations.

•   The device is designed for fixed installation indoors in dry 

conditions.

•   When connecting the device, ensure it has been discon-

nected from the power supply.

•   The device must not be opened. Faulty devices should be 

returned to the manufacturer.

•   When planning and erecting electrical systems, observe 

the specifications and regulations of the relevant country.