Installation and Operating Instruction for

 

B.E.G.

-

Occupancy detectors 

PD9-M-2C

3.   PD9-M-2C:   

Settings carried out 

using remote control 

(optional) 

Remote control 

LUXOMAT

®

 

IR-PD-2C 

1. Check Battery:

  

Open battery compartment 

by pressing the plastic springs 

together and removing the 

battery-holder.

 1. Mounting preparations 

 

Work on the 230 V mains supply 

may only be carried out by quali-

fied professionals or by instructed 

persons under the direction and 

supervision of qualified skilled elec-

trical personnel in accordance with 

electrotechnical regulations.

 

Disconnect supply before installing! 

 

When in Master/Slave mode of 

operation, the Master-appliance  

must always be installed at the  

location where there is least  

daylight.

2a. Installation 

Option:

The 

LUXOMAT

®

 PD9-M-1C 

+HVAC enters an initial 

60-second self-test cycle, 

when the supply is first con-

nected. The occupancy detec-

tor is ready for operation.

2c. Self test cycle

B.E.G.

LUXOMAT

®

 PD9-M-2C

2b.  Connecting terminals

7. Range of Coverage

In case the sensing area of the 

LUXOMAT

®

 PD9-M-2C is too large or 

areas are being covered that should not 

be monitored, the range can be reduced 

or limited through use of the enclosed 

masking clips.

6.  Exclude sources of  

interference

Walking across

Walking towards

Seated

quer zum Melder gehen 
frontal zum Melder gehen
Unterkriechschutz

PD9-M-2C

8.   Dimensions

HKL

max

3A

N

L‘

L

S

R

Sensor

OUT

IN

165 mm

24 mm

24 mm

45

25

 

12

16

PD9-M-2C

GB

10 m

6 m

4 m

10 m

360°

2,50 m

RJ

2

3

1

Wall bracket for remote control 

IR-PD-2C 

An adhesive film for the surface of the 

IR-PD-2C is included with the device. If 

required, this can be used for any 

B.E.G.

 

remote control with 27 keys.

In order to benefit from the whole range 

of functions of the PD9-M-2C, please 

order separately the remote control 

IR-PD-2C.

IR-PD-2C - 92475

4.  Settings by remote control IR-PD-2C 

Unlocking device – Activation of the  

programming mode

Locking device – Exit programming mode

  

The device is not suited for safe disconnection of the 

mains supply

Change between fully automatic and semi  

automatic mode (HA)

Luminance set point for channel 1 

20 - 1000 Lux

Automatic reading in the current light value as 

new luminance set point

Change between motion detector and  

photo electric switch

Increase the current light level by  

20 resp 50 Lux

Light ON/OFF

Resetting when 

open:  

Deletes all 

values set with 

the remote con-

trol, light OFF. 

After reset the 

default settings 

are activated. 

(500 Lux, 10 min 

light channel and 

15 min HVAC 

channel)

 

or

1000

20

to

+

Follow-up time channel 1 (light)  

5 - 30 min. or impuls
Follow-up time channel 2 (HVAC)  

5 - 120 min. or impuls

to

LED ON/OFF (by holding down the push button)

Detection sensitivity reduced or normal

Daytime operation, detector only  

activated by motion

or

PI R

CdS

Permanent protection against sabotage

white LED flashes

w

hen c

hoo

sing CdS

or

��

���

120 

min

min

max

50

Lux

1500

Lux

ON

OFF

t < 5 s

��

���

min

��

���

��

���

HA

ON/OFF

The detector has been 

designed and developed 

specifically for installation 

in suspended ceilings.

 A circular opening of 

diameter min. 34 mm 

must be produced in the 

ceiling. 

Having connected the 

cables in accordance with the regulations, connect the 

power supply via the RJ12 plug. Therefore, open the 

power supply with the help of the screws and close it 

afterwards. After that, put the power supply through the 

opening in the ceiling and mount the sensor onto the 

ceiling according to figure.

34 mm

5.  Key functions in closed state

Light ON/OFF during the detection of 

motion plus follow-up time; Activation 

of the 12 h-ON/OFF-function by 

holding down the push button

Switches channel off and is immedi-

ately active again, exits all timers, 

interruption of light measurement

Permanent protection against sabotage  

This function blocks the unit perma-

nently. This operating mode can only be 

activated during the period of 5 seconds 

(white LED flash) after pressing the “Lock“ 

button. The procedure for leaving this 

mode is as follows: 

 

1. Switch off the current

 

2.  Apply current for 31 - 59 seconds 

 3. 

Switch off the current again

 

4.  Apply current, wait for selftest 

cycle

 5. 

Open detector

Changes to “open” state

Activation/Deactivation of the test 

function

Confirmation

t < 5 sec.

max

50

Lux

1500

Lux

ON

OFF