9. Settings by remote control IR-PD-2C
10. Key functions in closed state
Unlocking device – Activation of the programming mode
Locking device – Exit programming mode
Change between fully automatic
and semi automatic mode (HA)
Luminance set point for channel 1
20 - 1000 Lux
Automatic reading in the current light value as new
luminance set point
Change between motion detector and photo electric
switch
Increase the current light level by
20 resp. 50 Lux
Light ON/OFF
HA
ON/OFF
Permanent protection against sabotage
This function blocks the unit permanently. This operat-
ing mode can only be activated during the period of
5 seconds (white LED flash) after pressing the “lock“
button. The procedure for leaving this mode is as
follows:
1. Switch off the current
2. Apply current for 31 - 59 seconds
3.
Switch of the current again
4. Apply current, wait for selftest cycle
5.
Open detector
Light ON/OFF during the detection of motion plus
follow-up time;
Activation of the 12 h-ON/OFF-function by holding
down the push button
Activation/Deactivation of the test function
Switches channel off and is immediately active again,
exits all timers, interruption of light measurement
Conirmation
Changes to “open“ state
Resetting when
open:
Deletes all
values set with
the remote con-
trol, light OFF.
Potentiometer
and DIP switches
are enabled for
setting.
or
to
+
Follow-up time ch1 (light)/
ch2 (HVAC) 5 - 30 min. resp.
120 min. or impulse
(switch-on delay channel 2: 5 min.)
��
���
to
LED ON/OFF (by holding down the push button)
or
Detection sensitivity reduced or normal
��
���
5
min
Daytime operation, detector only activated by motion
or
PI R
CdS
Permanent protection against sabotage
White LED lashes
w
hen c
hoo
sing CdS
8. Putting into operation of the remote
control IR-PD-2C
(optional)
Check Battery:
Open battery compartment
by pressing the plastic springs
together and removing the
battery-holder.
Caution:
Settings with remote control supersede
the settings by potentiometers.
1
2
2000
1200
600
200
40
16 10
5
2
1
30
15
TEST
7. Reset and default settings
1. Default settings
If the potentiometers are in the “Test“
and “Sun“ position and the detec-
tor is unprogrammed, the factory
program is activated: 500 Lux and
10 min.
2. Reset
If both potentiometers are returned to
the ”Test“ and “Sun“ setting from any
other position, a reset is executed. All
values programmed with the remote
control are deleted.
t < 5 sec.
t < 5 sec.
6. Putting into operation / Settings
Initialisation
In the first 60 seconds after connecting the power supply the
LUXOMAT
®
PD4-M-2C will go through a self test cycle. During this time the device
doesn´t respond to movement, but will stay on the status depending on the
selected initialization mode on or off (INI OFF or ON).
Warning: In the Ini-OFF mode, does not switch on lights at power start
up. After 60 seconds, detector would switch on lights on upon detect-
ing movement.
Potentiometer 1 – Adjustment twilight-switch for channel 1
“Light“
The switch-on value for the light can be set at between 10 and
2000 Lux. Using the potentiometer, the luminance set points
can be set as desired.
Symbol
:
Night operation
Symbol
:
Day/Night operation
Determining the current brightness
Set potentiometer 2 to the „Test“ setting. The green LED lights
up permanently as soon as the value set at the potentiometer
exceeds the current measured brightness.
Potentiometer 2 – Adjustment follow-up time channel 1 “Light“
Symbol
TEST
: Test mode, reacts on motion only. Every move-
ment switches on the light for a period of 2 seconds, switching
it off for a period of 2 seconds. The time can be set infinitely
variably at between 15 sec. and 16 minutes.
Potentiometer 3 – Follow-up time for appliance-control
The time can be set infinitely variably at between 5 minutes and
120 minutes. After 15 minutes the switch-on delay is activated.
This is around 5 min. If there are not detected any further move-
ments within this period, the switch-on delay starts again.
Symbol :
Impulse = 2,5 sec.
Symbol
A
:
Alarm impulse = 2 sec.
Alarm impulse
In order to set off an alarm impulse, at least 3 movements
within 9 sec. have to be detected.
The potentiometer settings are overriden using the remote control.
2000
1200
600
200
40
16 10
5
2
1
30
15
TEST
120 60
50
40
30
15
10
A
5
Option: Remote control IR-PD-2C(-S)
(to be used with IR-PD)
Wall bracket for remote control
An adhesive film for the surface of the IR-PD-2C-S
is included with the device. If required, this can be
used for any
B.E.G.
remote control with 27 keys.
In order to benefit from the whole range of func-
tions of the PD4-M-2C, please order separately the
remote control IR-PD-2C.
LUXOMAT
®
PD3
B.E.G.
B.E.G.
LUXOMAT
®
B.E.G.
LUXOMAT
®
500
200
400
100
20
IR-PD-2C-S
ON/OFF
H A
min
30
min
60
min
120
B.E.G.
LUXOMAT
®
R2
R1
R1
Film IR-PD-2C-S
IR-PD-2C - 92475
��
���
9s
2s
LED ON
LED OFF
Pulse spacing PD-Slave
2 or 9 seconds can be set for the pause
between 2 pulses sent to the master. The
setting can be made with activated ( ) or
deactivated ( ) LED indicator.
For devices with a separate slave input, 2 sec.
can be set.
120
min
5
min
1000
20
!