Installation and Operating Instruction for 

B.E.G.

 - Occupancy detector PD4-M-2C-SM/-FC/-FM

LUXOMAT

®

PD4-M-2C/PD4-S

GB

2a.     Installation  LUXOMAT

®

  

PD4-M-2C-SM

3a.  Hardware configuration SM 

Position LED’s and potentiometers

4a.  Position potentiometers DIP-Switch SM

5. DIP-switch functions

DIP-
switch

ON

OFF

1

Semi automatic mode

 Fully automatic mode

2

LED OFF

 LED ON

3

Corridor mode

 Standard mode

DIP

OFF

ON

1
2

3

A circular opening of 
diameter 68 mm must first 
of all be produced in the 
ceiling.

Having connected up the 
cables in accordance with 
regulations, the detector is 
inserted into the opening 
as shown in the drawing 
opposite and fixed into 
position with the assistance 
of the spring clip.

2b.      Installation  LUXOMAT

®

  

PD4-M-2C-FC

The detector can be installed 
in conventional inlet-sockets 
mounted on the ceiling. The as-
sembly plate enclosed must be 
stripped off prior to installation 
and secured to the ceiling using 
4 screws. 
Having connected up the 
cables in accordance with 
regulations, the detector can be 
placed in position as shown in 
the drawing opposite and, ap-
plying a little pressure, can then 
be locked into position with the 
assistance of the spring clips.
( For connections please see 

pt. 22!)

2c.      Installation  LUXOMAT

®

  

PD4-M-2C-FM

B.I.T

.

Q.C
.

PASSED

1

LED 1 green
LED 2 white
LED 3 red

3b.  Hardware configuration FC 

Position LED’s and potentiometers

Potentiometer 1 Lux   Channel1
Potentiometer 2 Time Channel1
Potentiometer 3 Time Channel2

LED 1 green
LED 2 white 
LED 3 red

3c.  Hardware configuration FM 

Position LED’s and potentiometers

Potentiometer 1 Lux   Channel1
Potentiometer 2 Time Channel1
Potentiometer 3 Time Channel2

 DIP 1    

Fully automatic/semi automatic mode

 

DIP 2

 

LED ON/OFF

DIP 3

  

Change between corridor mode and standard mode

 

The DIP switch settings are overriden using the remote control. 

4b.   Position DIP-Switch FC

S    

L    L         

R

Rel2

N

Rel1

230V

AC ±10%

50-60Hz

False ceiling mounting

ON

OFF

DIP

1

2

3

DIP 1   

Fully automatic/semi automatic mode

 

DIP 2

 

LED ON/OFF

DIP 3

  

Change between corridor mode and standard mode

 

The DIP switch settings are overriden using the remote control. 

4c.  Position DIP-Switch FM

S    

L    L         

R

Rel2

N

Rel1

230V

AC ±10%

50-60Hz

Flush mounting

ON

OFF

DIP

1

2

3

Corridor function:

 After deactivation by an external push 

button, the detector switches off and returns to automatic 
mode after 5 sec.

 
The DIP settings are enabled again by:
• Adjusting the DIP switches when closed
• Reset with test sun setting at the potentiometers
• Reset when open

closed

open

 1. Mounting preparation 
 

Work on the 230 V mains supply 
may only be carried out by quali-
fied professionals or by instructed 
persons under the direction and 
supervision of qualified skilled 
electrical personnel in accordance 
with electrical regulations.

Disconnect supply before installing!

The device is not suited for safe 
disconnection of the mains supply.

When in Master/Slave mode of 
operation, the Master-appliance must 
always be installed at the location 
where there is least daylight.

The detector must be installed 
on a solid and level surface. 
The circular cover ring 
must be removed prior to 
assembly. To do this, twist the 
lens anticlockwise through ap-
proximately 5° and lift off.

Having connected up the 
wires in accordance with 
regulations, secure the 
detector with 2 screws. After 
installation replace the lens 
and lock (turn clockwise). 
Mains to be connected.

LED 1 green
LED 2 red 
LED 3 white

Potentiometer 3 Time Channel2
Potentiometer 2 Time Channel1
Potentiometer 1 Lux   Channel1

DIP 1   

Fully automatic/semi automatic mode

 

DIP 2

 

LED ON/OFF

DIP 3

  

Change between corridor mode and standard mode

 

The DIP switch settings are overriden using the remote control. 

Surface mounting

OFF

ON

VA

LED

HA

COR

ON

OFF

DIP

40

15

30

1

2

5

10

16

TES

T

120

A

5

60

50

40

30

15

x

1

2

3

1

2

3

1

2

3

1

2

1

2

3

3

40

15

30

1

2

5

10

16

TES

T

120

A

5

60

50

40

30

15

x

40

TES

x

1 2 3

Содержание LUXOMAT PD4-S Series

Страница 1: ...2 LED ON OFF DIP 3 Umschalten Normalbetrieb Korridorbetrieb Die DIP Schalter Einstellungen werden mit der Fernbedienung berschrieben 4c Position DIP Schalter UP S L L R Rel2 N Rel1 230 VAC 10 50 60 H...

Страница 2: ...otentiometer aus einer beliebigen Position in die Stellung Test und Sonne gebracht werden wird ein Reset ausgef hrt S mtliche mit der Fernbedienung programmier ten Werte werden gel scht t 5s t 5s 6 In...

Страница 3: ...h werden kurzzeitige Helligkeitsschwankungen ausgeglichen 12 Ausschaltschwelle Helligkeit Die Funktionen Korridor und 12 h Licht AN AUS schlie en sich gegenseitig aus Sind beide aktiviert verh lt sich...

Страница 4: ...Slave rot blinkt schnell IR Befehl wei blinkt einmal IR Befehl ffnen und Sabotage aktiv wei und gr n blinken einmal lang PD4 M 2C new M HKL Funktion optional T1 NO Taster f r Halbautomatikbetrieb Sla...

Страница 5: ...tch FC S L L R Rel2 N Rel1 230 VAC 10 50 60 Hz False ceiling mounting ON OFF DIP 1 2 3 DIP 1 Fully automatic semi automatic mode DIP 2 LED ON OFF DIP 3 Change between corridor mode and standard mode T...

Страница 6: ...Settings Initialisation In the first 60 seconds after connecting the power supply the LUXOMAT PD4 M 2C will go through a self test cycle During this time the device doesn t respond to movement but wi...

Страница 7: ...on for 5 min with dark and motion 2 Light OFF for 2 sec 3 Internal calculation of the switch off value 2 If the eye push button is pressed the switch off threshold is recalculated See also Remote con...

Страница 8: ...and OFF 4 sec Corridor and semi automatic mode active White ON 4 sec and OFF 1 sec Too bright detected Green flashes Light measurement active Green flashes once every 10 sec 12 h ON OFF func tion acti...

Отзывы: