background image

LUXOMAT

®

 PD4-S-DAA4G

EN

Installation and Operating Instruction for 

B.E.G.

PD4-S-DAA4G

1. Product information

• 

Slave occupancy detector designed for PD4-M-DAA4G 

compact DALI system

• 

For expansion of a master device’s detection area

• 

When movement is detected, a switch pulse is sent to the 

master independent of ambient light level

• 

Simple mounting

• 

Automatic test mode via master device

• 

Plug & Play - no setup required

2. Operation

Work on electrical equipment should only be undertaken 

by qualified electricians or by trained personnel under the 

instruction and supervision of a trained electrician, according 

to the regulations for electrical installation

Turn off the mains supply before fitting

This device is not to be used to isolate other equipment from 

the mains supply

After inserting the connection cable, fit the supplied cover to 

the detector
The push button inputs and the D+/D- terminals must not be 

connected to the mains supply

3. Operation

3.1 General

The PD4-S-DAA4G is for expanding the detection area of a  

PD4-M-DAA4G. Motion detection is based on passive infrared 

technology. If people, animals or other heat sources move within 

the detection area, the detector forwards motion detection events to 

a PD4-M-DAA4G using a 

B.E.G. 

DALI protocol.

See Figure 3.1: Detection diagram

3.2. System characteristics
A maximum of four PD4-S-DAA4G can be controlled by one  

PD4-M-DAA4G.

 Ideally, the detection areas should overlap by 

about 30%. Power supply is via the DALI bus, with current consump-

tion of about 7 mA on average. The DALI bus must only be supplied 

with the required voltage via the DALI power supply integrated into 

the PD4-M-DAA4G.

See Figure 3.2: Circuit diagram

3.3 In use

The PD4-S-DAA4G sends a 

B.E.G.

 DALI telegram to the master 

every 30 seconds, if motion is detected within this 30-second 

period. If the master is in test mode, and the slave detects motion, it 

sends a 

B.E.G.

 DALI telegram to the master every 2 seconds. After 

3 minutes, the slave device automatically reverts to normal mode.

During the PD4-M-DAA4G addressing phase, no-one should 

remain in the detection area of the PD4-S-DAA4G, as otherwise 

there is a risk that not all DALI electronic ballasts will be detected 

and addressed. 

To be absolutely sure that no DALI telegram is sent from slave 

to master during addressing of the DALI electronic ballasts, it is 

recommended that the slaves are only connected to the DALI bus 

after addressing of all DALI electronic ballasts.

4. Mounting

4.1. General

The ideal mounting location is inside, 2.5 to 3 metres high, on the 

ceiling. Ventilation units should not be in the immediate vicinity of 

the detector, as otherwise “false alarm” motion detection events 

may be triggered. 

4.2. Connecting for false ceiling

A circular opening of diameter 68 mm must first of all be produced 

in the ceiling. Having connected up the cables in accordance with 

regulations, the detector is inserted into the opening as shown in 

the drawing opposite and fixed into position with the assistance of 

the spring clip.

4.3  Connecting for surface

The detector must be fixed on a smooth, solid surface. Before moun-

ting, the lens must be removed. Turn the lens about 5° anticlockwise 

and remove it. Undoing two screws allows the detector to be 

removed from the socket. After properly connecting the wiring, and 

attaching the socket to the ceiling with 2 screws, the detector must 

be reattached to the socket with 2 screws. Then reattach the lens, 

turning it clockwise.

See Figure 4.3: Surface mounting

4.4 Light sensor

The light sensor on the exterior of the cover ring is intended for 

future applications.

See Figure 4.4: Light sensor LED

5. Self-test cycle

In the first 60 seconds from when the mains voltage is turned on, 

the detector runs through a self-test cycle. During this period, the 

device does not react to movement.

6. Initial operation

The PD4-S-DAA4G requires no setup or addressing, and is  

therefore ready to use.

7. Blocking out sources of interference

In order to block out sources of interference, for example copiers 

or air conditioning outlets, there is an option to fit clip-on covers 

to the lens.

See FIGURE 7: Exclude sources of interference

8. LED Indication

Nr.

Indication

white

1

Self-test cycle

Blinking

2

Movement detected

Short ON

9. 

Article / Part nr. / Accessory

Typ

Part 

Info

PD4-S-DAA4G-FC

92721

Slave, version for false 

ceiling mounting

PD4-S-DAA4G-SM

92759

Slave, version for surface 

mounting

10. 

Technical data

Power supply:

 

max. 22 V DC over DALI-Bus

Area of coverage:

 

 

circular, 360°

Range of coverage:

 

Ø 24 m transverse

  

 

Ø 8 m towards

  

 

Ø 6,4 m seated

Protection type/class:

 

SM IP54, FC IP20 / II / CE

Ambient temperature:

  

 

-25°C / +50°C

Dimensions FC :  

Ø 98 x 96 mm

Dimensions SM :  

Ø 101 x 69 mm

Housing:

  

Polycarbonate, UV-resistant

Puls interval: 

  

30 seconds (2 seconds in the test mode 

for a period of 3 minutes) Slave

DALI:  

  

Power supply via DALI bus of 

 

 

 

 PD4-M-DAA4G   

Power consumption: 

about 7 mA  

maximum 4 slaves in combination with 

a PD4-M-DAA4G

 

Declaration of conformity

This product respects the directives concerning
1.   electromagnetic compatibility (2004/108/EU)
2. 

low voltage (2006/95/EU)

3. 

 restriction of the use of certain hazardous substances in 

electrical and electronic equipment (2011/65/EU)

11. Potential problems

There can be many causes of problems with lighting control. The 

following shows a selection of possible causes. 

Current draw of connected DALI units too high

In designing your system, please take into account the total current 

draw of all DALI units (electronic ballasts and any slave devices). 

The DALI power supply integrated into the PD4-M-DAA4G can 

provide a stable supply voltage when total current draw of all DALI 

units is 150 mA. Each DALI electronic ballast requires 2 mA. A 

slave device requires 7 mA.

Too many slave devices connected

If more than 4 slave devices are connected to the PD4-M-DAA4G 

DALI compact system, unexpected lighting control errors can occur.

Heat sources in vicinity

If, for example, the detector is in the immediate vicinity of 

ventilation outlets or a projector, the warm air coming from these 

can trigger motion detection. Position the detector sufficiently far 

from potential sources of interference, such as ventilation outlets, 

projectors, video units, copiers, printers etc.

M

A

N 8

60

– P

D

4-

S-

D

A

A

4G

_EN

–2

– 2

50

81

5

!

!

!

!

!

PD4-S-DAA4G_120515.indd   1

28.08.2015   11:18:15