Installation and Operating Instruction for 

B.E.G.

-Occupancy detectors

 PD4-M-DIM-SM/-FC/-FM

 1. Mounting preparations 

 

Work on the 230 V mains supply 

may only be carried out by quali-

fied professionals or by instructed 

persons under the direction and 

supervision of qualified skilled 

electrical personnel in accordance 

with electrical regulations.
Disconnect supply before installing!
The device is not suited for safe 

disconnection of the mains supply.

When in Master/Slave mode of op-

eration, the Master-appliance must 

always be installed at the location 

where there is least daylight.

LUXOMAT

®

PD4-M-DIM

GB

4. DIP switch functions

DIP

OFF

ON

1

2

3

The DIP settings are enabled again by

• Adjusting the DIP switches when closed

• Reset with test sun setting at the potentiometers

• Reset when open

Corridor function:

 After deactivation by an external push button, the 

detector switches off and returns to automatic mode after 5 sec.

Function LEDs OFF:

 In the open state and in test mode, the LEDs are 

always ON.

3.    Position  DIP-switches

The DIP switch settings are 

overriden using the remote 

control. 

Surface mounting

1

2

3

OFF

ON

VA

LED

HA

COR

ON

OFF

DIP

x

7. Option:

Wall bracket for remote

control IR-PDim 

IR-PDim 

8. Settings by remote control

Unlocking device - Activation of 

the programming mode

Resetting when-

open: 

Deletes all 

values set with 

the remote con-

trol, light OFF.

or

Start of the dim process

Luminance set point for 

constant light control

50

Lux

to

1500

Lux

1

min

to

30

min

1

min

to

60

min

max

50

Lux

1500

Lux

ON

OFF

max

50

Lux

1500

Lux

ON

OFF

or

max

50

Lux

1500

Lux

ON

OFF

9s

2s

LED ON

LED OFF

25 22

18

16

10

3

1

TEST

6

30

R1

120 6050

40

30

15

10

A

16 10

5

2

1

30

15

TEST

2000

1200

600

200

40

5

60

5

10

30

50

ON

OFF

1

1

2

2

25 22

18

16

10

3

1

TEST

6

30

R1

120 6050

40

30

15

10

A

16 10

5

2

1

30

15

TEST

2000

1200

600

200

40

5

25 22

18

16

10

3

1

TEST

6

30

R1

2000

1200

600

200

40

   

 

False ceiling mounting

Flush mounting

1

2

3

ON

OFF

DIP

2a.  Installation of the LUXOMAT

®

  

PD4-M-DIM-SM

A circular opening of 

diameter 68 mm must first 

of all be produced in the 

ceiling.
Having connected up the 

cables in accordance with 

regulations, the detector is 

inserted into the opening 

as shown in the drawing 

opposite and fixed into 

position with the assis-

tance of the spring clip.

2b.  Installation of the LUXOMAT

®

  

PD4-M-DIM-FC

The detector can be installed 

in conventional inlet-sockets 

mounted on the ceiling. 
The assembly plate enclosed must 

be stripped off prior to installa-

tion and secured to the ceiling 

using four screws and ensuring 

that it flat. Having connected up 

the cables in accordance with 

regulations, the detector can be 

placed in position as shown in 

the drawing opposite and, ap-

plying a little pressure, can then 

be locked into position with the 

assistance of the spring clips.
(Please refer to the connection 

diagrams)

2c.  Installation of the LUXOMAT

®

  

PD4-M-DIM-FM

B.I.T

.

Q.C
.

PA

SSED

1

close

open

The detector must be in stalled 

on a solid and level surface. 

The circular cover ring 

must be removed prior to 

assembly. To do this, twist the 

lens anticlockwise through 

approximately 5° and lift off. 
Having connected up the 

wires in accordance with 

regulations, secure the 

detector with 2 screws. After 

installation replace the lens 

and lock (turn clockwise). 

Mains to be connected

.

max

50

Lux

1500

Lux

ON

OFF

optional

optional

optional

t < 5 sec.

Light on / off when closed  

=> (see page 2, point 12)
Dimming in the closed state 

=> (see page 2, point 11)
Test operation in the closed condition to enable 

Disable the test mode: press reset
Resetting when closed 

The lighting relay is switched off, i.e. opened and the follow-up times 

reset.

Permanent protection against sabotage 

This function blocks the unit permanently (green LED is illuminated). This 

operating mode can only be activated during the period of 5 seconds after 

pressing the “lock“ button. This status will only permit actuating the function 

“Light on/Light off”. The procedure for leaving this mode is as follows:
 

1. Switch off the current 

 

2. Apply current for 31 - 59 seconds    

 

3. Switch of the current again 

 

4. Apply current 

 

5. Open detector

Dim in the open state

 

To set a target value, proceed as follows (example workplace):Place one 

lux meter flat on the desk. Set the light with the help of remote control IR-

PDim by pressing the buttons „max“ or „min“ for starting the dim process. 

Wait until the desired light level is reached. 

Confirmation by the preset value 

 

Light during the initialization 

The light is on by default in the initialization time. 

On / off with the „Light“ button during Initialization. The final condition 

is then active.

Follow-up time orientation light ON / OFF when open

 

Note:

 Also during the orientation phase of the light constant light control is 

active: With sufficient brightness is <20% dimmed and turned off the lights 

if necessary.

max

50

Lux

1500

Lux

ON

OFF

t < 5 s

9. 

Explanation of the remote control button functions

max

50

Lux

1500

Lux

ON

OFF

max

50

Lux

1500

Lux

ON

OFF

Stop of the dim process and 

reading 

in the current light value as new 

luminance set point

DIP-

switch

ON

OFF

1

Semi automatic mode

 Fully automatic mode

2

LED OFF

 LED ON

3

Corridor mode

 Standard mode

 5. Putting into operation / Settings 

Initialization

In the first 60 seconds after connecting the power supply the 

LUXOMAT

®

 

PD4-M-DIM will go through a self test cycle. During this time the device 

doesn´t respond to movement, but will stay on the status depending on the 

selected initialization mode on or off (INI OFF or ON).

Warning: In the Ini-OFF mode, does not switch on lights at power start 

up. After 60 seconds, detector would switch on lights on upon detecting 

movement.

Follow-up time for light control

 The time can be set infinitely variably at between  

1 and 30 minutes.   

Symbol 

TEST

: Test mode (Every movement switches on the light 

for a period of 1 second, switching it off for a period of 2 

seconds after that regardless of the level of brightness)

Twilight-switch for light control (relay 1)

The switch-on value for the light can be set at between 10 and 

2000 Lux. Using the rotary control, the luminance set points can 

be set as desired. 
Symbol  : 

Night-time operation

Symbol 

:  

Daytime/Night-time operation

Orientation lighting 

This rotary controller serves to determine the working time of 

the orientation lighting (fixed to 20 %).

“ON” for permanent orientation lighting.  

“OFF” for deactiviation of orientation lighting.

Pulse spacing PD-Slave

2 or 9 seconds can be set for the pause between 2 pulses sent 

to the master.  The setting can be made with 

activated 

( ) or 

deactivated ( ) LED indicator.
For devices with a separate slave input, 2 sec. can be set.

6.  Settings carried out using remote 

control (optional)

Remote control 

LUXOMAT

®

 IR-PDim

1. Check Battery:

  

open battery compartment by pressing the 

plastic springs together and removing the 

battery-holder.

2.   IMPORTANT 

Please pay attention, that the setting is 

Potentio-meter 1 at “TEST” and Potentiometer 

not

 at “SUN”. All values which have 

been programmed using the remote control 

will be deleted in the event of power failure 

in the position “TEST/SUN”. Please switch 

Potentiometer 2 over to “MOON” or any 

other value.

Caution:

  

Settings with remote control supersede the 

settings by courtesy of potentiometers.

Preset/user mode  

=> (see page 2, point11)

Follow-up time light

Orientation lighting and its

follow-up time

Orientation lighting ON/OFF

20 % of the nominal light

Fully automatic/semi automatic 

mode => (see page 2, point10) 

Locking device – Exit programming 

mode

Permanent protection against 

sabotage

LED flashes

In the initialization period 

During initialization phase/self test cycle 

Lights can be set to on or off status during initialization(60 Seconds) by using 

INI OFF/ON mode. 

max

50

Lux

1500

Lux

ON

OFF

!