 3. Putting into operation / Settings 

Follow-up time for light control

 The time can be set infinitely variably at between  

15 seconds and 16 minutes. 
Symbol  : 

impulse < 1sec.

 Symbol 

TEST

:   Test mode 

(Every movement switches on the light for a period of 1 

second, switching it off for a period of 2 seconds after that 

regardless of the level of brightness.)

Twilight-switch for light control (relay 1)

The switch-on value for the light can be set at between 10 

and 2000 Lux. Using the rotary control, the luminance set 

points can be set as desired. 
Symbol  : 

Night-time operation

Symbol  :  

Daytime/Night-time operation

Installation and Operating Instruction for 

B.E.G.

 - Occupancy detectors PD4-M-1C-FC/-FM

The detector can be installed 

in conventional inlet-sockets 

mounted on the ceiling.

The assembly plate enclosed 

must be stripped off prior to 

installation and secured to 

the ceiling using 4 screws 

and ensuring that it is not 

laterally transposed. 

Having connected up the 

cables in accordance with 

regulations, the detector can 

be placed in position as 

shown in the drawing op-

posite and, applying a little 

pressure, can then be locked into position with 

the assistance of the spring clips.

2b.  Installation of the LUXOMAT

®

 

PD4-M-1C-FM

Unlocking device

Lock device

4. Settings carried out using remote control (optional)

Remote control LUXOMAT IR-PD

1. Check Battery:

 

open battery compartment by pressing the 

plastic springs together and removing the 

battery-holder.

2.  IMPORTANT 

Please pay attention, that the setting is Potentio-

meter 1 at “TEST” and Potentiometer 2 

not

 at 

“SUN”. All values which have been programmed 

using the remote control will be deleted in the 

event of power failure in the position “TEST/

SUN”. Please switch Potentiometer 2 over to 

“MOON” or any other value.

Caution:

 

Settings with remote control supersede the 

settings by courtesy of potentiometers.

LUXOMAT

®

PD4-M-1C

 1. Mounting preparations
 

Work on the 230 V mains supply 

may only be carried out by qualified 

professionals or by instructed persons 

under the direction and supervision 

of qualified skilled electrical person-

nel in accordance with electrotechni-

cal regulations.

 

Disconnect supply before installing! 

 

When in Master/Slave mode of 

operation, the Master-appliance  

must always be installed at the  

location where there is least  

daylight.

Lock device

Test mode 

Reset to deactivate

Resetting when closed

The lighting relay is switched off, i.e.  

opened and the follow-up times reset.

Permanent protection against sabotage

This function blocks the unit permanently (green LED is illuminated). 

This operating mode can only be activated during the period of 

5 seconds after pressing the “lock“ button. This status will only  

permit actuating the function “Light on/Light off”.
The procedure for leaving this mode is as follows:

 

1. Switch off the current

 

2. Apply current for 31 – 59 seconds 

 

3. Switch of the current again 

 

4. Apply current 

 

5. Open detector

Light on/off

The light will remain switched on/off for as long as movements 

are detected in the areas of coverage. Once the last movement  

has been detected, the light will remain on for the duration of the 

follow-up time as per setting.  

The appliance will then return independently to the mode 

selected (Fully or Semi-automatic).

2a.  Installation of the LUXOMAT

®

 

PD4-M-1C-FC

The detector has 

been designed and 

developed specifi-

cally for installation in 

suspended ceilings.

A circular opening of 

diameter 68 - 70 mm 

must first of all be pro-

duced in the ceiling. 

Having connected up the cables in accordance 

with regulations, the detector is inserted into 

the opening as shown in the drawing opposite 

and fixed into position with the assistance of the 

spring clip.

Option:

Wall bracket for remote  

control IR-PD

��

���

max

50

Lux

1500

Lux

ON

OFF

max

50

Lux

1500

Lux

ON

OFF

����

���

��

���

��

���

max

50

Lux

1500

Lux

ON

OFF

Luminance set point

Automatic reading in the current light value  

as new luminance set point 

Individual light value 2 - 2500 Lux

Follow-up time (relay and channel 1) 

15 sec. up to 30 min.

Impulse function (relay and channel 1) 

1sec. ON, 9 sec. OFF

Preset/user mode

Fully automatic/semi automatic mode => (see page 2, point 5)

Semi automatic: red LED (flashing),  

Fully automatic: red LED on for ca. 3 sec.

Resetting when open 

All values which have been programmed using the remote 

control IR-PD are deleted, and those values which have  

been set by potentiometer are activated.

120 6050

40

30

15

10

A

16 10

5

2

1

30

15

TEST

2000

1200

600

200

40

5

120 6050

40

30

15

10

A

16 10

5

2

1

30

15

TEST

2000

1200

600

200

40

5

2c. Self test cycle

The product enters an initial 60-sec-

ond self-test cycle, when the supply 

is first connected. The occupancy 

detector is ready for operation.

GB