4 m
Installation and Operating Instruction
2a. Installation of the LUXOMAT
®
PD3-1C-SM
2b. Installation of the LUXOMAT
®
PD3-1C-FC
Sensor and power supply in one case
Power supply:
230 V~
±
10 %
Power consumption:
< 1W
Ambient temperature:
-25°C to +50°C
Degree of protection /class:
SM IP44, FC IP20 / II
Settings:
locally
Area of coverage:
circular 360°
Range of coverage Ø H 2.50 m / T = 18°C:
smaller movements 4 m / tangential 10 m / radial 6 m
Recommended height for mounting:
2 - 3 m
Light measurement:
mixed light, da artificial
light
Lux values - Potentiometer:
10 - 2000 Lux
• Channel 1 for light-connection
Type of contact:
NOC/with pretravel tungsten
contact
Contact load:
2000 W, 230 V~, cos
ϕ
=1 /
1000 VA cos
ϕ
= 0.5
Time-settings:
30 sec. - 30 min. / Test
Dimensions H x Ø [mm]
AP
DE
PD3-1C
52 x 106 84.5 x 80
Visible portion when built into ceiling:
15 x 80 mm
Version:
v.01
Declaration of Conformity:
The product complies with
the low voltage recommendation 2006/95/EC and the
EMV recommendation 2004/108/EC.
4. Technical data PD3-1C
5. Trouble shooting
1. Lamp does not light up
Lamp may be defect:
Replace lamps
No mains connection/power:
Check connection and mains fuse by qualified electrician
Incorrect setting of CDS twilight threshold:
Correct setting of CDS threshold
Lens of sensor unit obstructed by dirt or other objects:
Clean lens, remove objects
2. Lamp turns ON too late or detection range too small
PD3-1C is mounted too high:
Correct mounting if required.
3. Lamp stays ON continuously
Continuous thermal activity detected ie fan, central heat-
ing ducts, animals within detection area:
Remove heatsource. Check proper function of PD3-1C by
covering the fresnel-lens. After expiry of delay timer,
PD3-1C has to turn OFF lighting.
PD3-1C
connected in parallel to a manual override
switch:
Connect switch correctly
4. Unintended switching of light
Movement of heat source within detection area:
Check on presence of animals, fans or heaters
The detector must be installed on a
solid and level surface. There is no
need for frames.
For mounting remove lens (C) (turn
anticlockwise). Fasten the mounting
base to the ceiling.
Having connected up the wires in accordance with
regulations, secure the detector with 2 screws as per the
illustration above.
1. Mounting preparations
Work on the 230 V mains supply may only be carried out by quali-
fied professionals or by instructed persons under the direction and
supervision of qualified skilled electrical personnel in accordance
with electrotechnical regulations.
Disconnect supply before installing!
The detector has been designed
and developed specifically for
installation in suspended ceilings.
A circular opening of diameter
68 mm must be cut into ceiling.
Having connected up the cables in accor dance with
regulations, the detector is inserted into the opening as
shown in the drawing above and fixed into position with
the assistance of the spring clips.
7. Article / Part nr.
6. Range of Coverage
quer zum Melder gehen
frontal zum Melder gehen
Unterkriechschutz
Walking across
Walking towards
Smaller movements
1
2
3. Putting into operation / Settings
Initialization
In the first 60 seconds after connecting the power supply, the
LUXOMAT
®
PD3-1C goes through a self-check. During this time the
detector does not react to the movements, but the detector stays on
or off, depending on the choice of the initalization mode.
INI-OFF/ON
You can adjust, whether the detector stays on or off
during the first 60 seconds of the initialization mode.
Attention:
During INI-OFF the detector does not
switch on, after adding the power supply. Even a
movement brings the detector to switch on after 60
seconds.
Follow-up time for light control
The time can be set infinitely variably at between
30 seconds and 30 minutes.
Symbol :
impulse < 1sec.
Symbol
TEST
: Test mode
(Every movement switches on the light for a period of
1 second, switching it off for a period of 2 seconds
after that regardless of the level of brightness.)
Twilight-switch for light control
The switch-on value for the light can be set at
between 10 and 2000 Lux. Using the rotary control,
the luminance set points can be set as desired.
Symbol :
Night-time operation
Symbol : Daytime/Night-time operation
Adjusting sensitivity
For sensitivity adjustment of the detector, both in
the interior and the exterior range, the PD3-1C is
equipped with an additional knob (see pictures) for
excluding sources of interference, e.g. bad weather
conditions or draught air.
Max:
for interior use
(recognition of the slightest movements)
Min:
for exterior use
(exclusion of sources of interference)
120 6050
40
30
15
10
A
16 10
5
2
1
30
15
TEST
2000
1200
600
200
40
5
max.
min.
2
4
6
8
12
30
secs
30
mins
1
min
TEST
2000
1200
600
200
40
10 m
6 m
4 m
10 m
360°
2.50 m
1
2
3
3
Type
SM
FC
PD3-1C
92194
92197
ca. 68 mm
INI-
ON
INI-
OFF
!
B.E.G.
LUXOMAT
®
PD3-1C
RUS