1
2
e
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
Sensor and power supply in one case
Power supply:
230 V~ +6 %/-10 %
Power consumption:
< 1W
Ambient temperature:
-25°C to +50°C
Degree of protection /class:
SM IP54, FC and FM IP20 / II
Settings:
locally and by remote control
Light values - IR-PD:
10 - 2000 Lux
Extension of the detection area:
with Slaves
Area of coverage:
circular 360°
Range of coverage Ø H 2.50 m / T=18°C:
seated 2.50 m / tangential 10 m / radial 6 m
Recommended height for mounting:
2 - 3 m
Light measurement:
mixed light, da artificial light
Lux values - Potentiometer:
10 - 2000 Lux
• Relay/Channel 1 for light-connection
Type of contact
: NOC/with pretravel tungsten contact
Contact load:
2300 W, 230 V~, 10 A cos (
ϕ)
=1 /
1150 VA cos (
ϕ)
= 0.5
DIM-Output:
1 x (1-10 V)
Max. no. of series-connected electronic ballasts:
max. 50 electronic ballasts by one single supply with
max. 100 m cable run and a conductur cross-section of
0.75 mm²
Time-settings:
15 sec. - 16 min. (30 min. with remote
control) / test
Dimensions HxØ [mm]
SM
FC
FM
PD2-M-1C
50 x 98 84,5 x 80 65 x 98
Visible portion when built into ceiling:
34 x 79 mm
Technical data PD2-Slave
Electrical data same as above, but just one channel for
signaling motion detection.
Declaration of Conformity:
The product complies with
the low voltage recommendation 2006/95/EC and the
EMV recommendation 2004/108/EC
12. Technical data PD2-Master-1C
10. Wiring diagrams
Type
SM
FC
FM
PD2-M-1C
92550
92565
92555
LUXOMAT
®
Remote control:
IR-PD (incl. wall bracket)
92160
IR-PD-Mini
92159
Accessory:
BSK Ball basket guard
92199
Wall bracket for remote control as replacement 92100
Socket IP54
92161
9. Article / Part nr. / Accessory
M
A
N 5
62
8
– 1
41
20
9-
4
In case the sensing area of the
LUXOMAT
®
PD2-M-
1C-SM is too large or areas are being covered that
should not be monitored, the range can be reduced
or limited through use of the enclosed masking
clips (e).
8. Exclude sources of interference (PD2-M-1C-SM)
5. Fully / Semi automatic mode
(for IR-PD functions see page 1)
Fully automatic operation
In this operating mode, the lighting switches automati-
cally on and off for increased comfort, depending on
presence and brightness.
Semiautomatic operation
(Semiautomatic can only be activated via the remote
control!)
In this operating condition, in order to gain increased
savings, the lighting is energized only after being manu-
ally switched on.
Switch-off takes place automatically.
The semiautomatic mode basically behaves like the fully
automatic one. However, the difference is that switching-
on must always be carried out manually!
As many (closer-contact) buttons as desired can be wired
in parallel on the “S” button input (ON/OFF).
13. LED-functional indicators, fault-finding
The functional indicators in the case of the
LUXOMAT
®
PD2-M-1C-MASTER (red and green LED‘s)
Red LED indicating self-checking mode (over a period
of 60 seconds following mains‘-supply lock-on)
Flashing at intervals of 1 second
EEPROM/memory empty
Flashing rapidly
EEPROM/memory contains information
Red LED as an indicator of status
Flashing irregularly
Movements are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off
(dependent upon operating mode)
Not illuminated
Detector identifies dark, light on
(dependent upon operating mode)
Flashing extremely rapidly
Too bright / Too dark / Undefined
Red LED as an acknowledgement of receipt for
commands from the remote control
Illuminated for 2 seconds
Signal validly received
Illuminated for 0.5 seconds
Not-accepted command, detector blocked
Flashing extremely rapidly
Not-accepted command, occurs, for example, when
an attempt is made to input twilight-value are too
bright or too dark
Lights up for 3 seconds
Fully automatic mode
Flashing for 3 seconds
Semi automatic mode
Green LED as an indicator of status (only for status
“Permanent protection against sabotage”
)
Flashing irregularly
Movement are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off
(dependent upon operating mode)
Not illuminated
Detector identifies dark, light on
(dependent upon operating mode)
lluminated for 2 seconds
Signal validly received
(dependent upon operating mode)
7. Range of Coverage
6. Manual Switching
You can switch the lighting on and off manually by
pressing the pushbutton for a short time. It will stay on or
off as long as people are detected plus the configured
follow up time.
max
50
Lux
1500
Lux
ON
OFF
11. PD2-M-1C - Connections
Connection PD2-M-1C-SM
Connection PD2-M-1C-FC/-FM
NO
NO
N
R
L L
SLAVE
S
3A
NO
NO
N
R
L L
S
SLAVE
3A
N
quer zum Melder gehen
frontal zum Melder gehen
Unterkriechschutz
walking across
walking towards
seated
Master
Standard operation
Terminal connection for standard operation
S
Master
Standard operation
Terminal connection for standard operation
S
NO
NO
FC
L
N
N N L L R R
Master
Slave
Master-/Slave-operation with one Master and
several Slaves.
The Master is the only unit to read in the Lux levels and to
switch the connected loads. The Slave units will react on
motion only, independently of the Lux levels, by sending an
impulse via the dry contact, to the Master.
Terminal connection for Master-/Slave-operation
S
Master
Standard operation,
manual switching possible (NO-
contact to be pressed for approx. 1sec.) The potentio meters
not to be set on “Test“ or “Sun“ otherwise the preadjusted
values will get lost during this manual operation.
Standard operation with external push button
S
SM
SM
10 m
6 m
2.50 m
10 m
360°
2.50 m
1
2