BL4, BL4-C
93288, 93284
Operating Manual
25
10
Technical Data
10.1
General data
BL4 (93288)
BL4-C (93284)
Voltage
AC 110 – 240 V , 50/60 Hz
Power consumption
approx. 0.3 W
Terminal clamps
0.5 – 2.5 mm
2
, for solid one-wire conductors
Connection cable (recommended)
NYM 5 x 1.5 mm
2
Circuit breaker
max. 10 A
Detection area
vertical, 360°
vertical,
narrow for corridors
Mounting height min./max./recomm. 2 m / 5 m / 2.5 m
2.4 m / 2.6 m / 2.5 m
Range
(mounting height 2.5 m,
at ambient temperature 18 °C)
Walking across
Walking towards
Seated activity
max. Ø 19.0 m
max. Ø 6.4 m
max. Ø 5 m
max. 32.0 m
max. 16.0 m
Monitored area when moving across
the detector
284 m
2
at 2.5 m mounting
height
200 m
2
at 2.5 m mounting
height
Switch-on threshold
10 – 2000 Lux
Follow-up time
15 s – 60 min
Housing
Polycarbonate, UV-resistant
Protection class/degree of protection II / IP20
Dimensions H x Ø [mm]
84 x 104.5 mm
Ambient temperature
-25 °C – +50 °C
Relay contact
1 x µ contact, normally open/NO
Switching capacity
1000 W, cos
φ
= 1
500 VA, cos
φ
= 0.5
200 W LED
remote controllable
yes (with IR-BL)
Factory settings
Detection sensitivity
Follow-up time
Switch-on threshold
High
3 min
500 Lux
Nameplate
BL4 93288
IP20
10mm
0.5–1.5
50/60Hz
110–240V
500VA
1000W
μ
cos
φ
=1:
cos
φ
=0.5:
BL4-K/C 93284
IP20
10mm
0.5–1.5
50/60Hz
110–240V
500VA
1000W
μ
cos
φ
=1:
cos
φ
=0.5:
Содержание Luxomat BL4
Страница 1: ...Subject to technical changes Motion detector BL4 BL4 C Operating Manual 93288 93284...
Страница 14: ...Operating Manual BL4 BL4 C 93288 93284 12 2 3...
Страница 15: ...BL4 BL4 C 93288 93284 Operating Manual 13 4 2 3 Flush mounting with mounting set 93194 4 1...
Страница 16: ...Operating Manual BL4 BL4 C 93288 93284 14 2 3 4 5...
Страница 31: ...93284_93288_OP_MAN_BL4_en_V2 book 24 09 2020...