USA-EN
Installation and Operating Instruction for
B.E.G.
Controls - Occupancy sensor FLAT-P-PP-A-FC
FLAT-P-PP-A-FC
Controls
B.E.G.
1
1. Product information
•
FLAT primary sensor with PIR technology for use
with PP-A-J and PP-1-J power packs or proprietary
low voltage system
•
Designed for indoor locations
•
Up to 4 Secondary sensors may be connected
with a primary sensor to increase detection
coverage.
•
Spring clips for quick and easy installation in
suspended ceilings and light fixtures
•
5-year limited warranty
•
Masking blinds included
•
All programmable features can be adjusted via
B.E.G. Controls smartphone IR-Adapter and
Android or iOS app.
•
ROHS compliant
•
Photocell included as a standard feature
2. Operation with power pack
PP-A-J and PP-1-J
The FLAT with B.E.G. PP-A power pack detects both
motion and the ambient light level in the room
and then automates the lights according to the
parameters set by the installer and/or building
management. The integrated light sensor constantly
measures the ambient light and if the light level is
sufficient, the light will be switched off. If the ambient
light level is below the preset brightness level the
lights will be allowed to come on when the sensor
detects movement in the room.
When motion is detected in the room, the PP-A‘s
auxillary dry contact relay will send a signal to HVAC
or other systems indicating that the room is occupied.
With the integration of simple off the shelf, normally-
open momentary switches, the FLAT-PP-A can be set to
operate in vacancy mode via the auto/manual switch
selector on the power pack. The switches can be used
to turn off the lighting before the preset time out period.
3. Safety information
!
Work should be carried out by qualified pro-
fessionals or by instructed persons under the
direction and supervision of qualified skilled
electrical personnel in accordance with electri-
cal regulations.
!
The device is not to be used to isolate other
equipment from the mains supply!
4. Mounting
Select sensor(s) mounting location based on room
dimensions and sensor coverage pattern. Avoid
placing sensor(s) less than four feet away from a
heat and/or ventilation
sources. Avoid placing
sensor(s) where view
will be directed outside
of intended controlled
space, this to prevent
outside sources from
activating sensor(s). A
circular opening of di-
ameter 1.73 in/44 mm
must be produced in
the ceiling.
Connect the sensor to
the power pack using the RJ12 connector. Pass sen-
sor’s RJ12 connector through ceiling opening. Next,
squeeze spring clips through ceiling opening. Sensor
should clip securely into place. (See figure)
For mounting into luminaires use the supplied clamp
ring and remove the spring clips.
!
When using primary and secondary devices,
please mount the primary device at the place
with the least amount of natural light.
5. Position LEDs
LED 1 green/red
6. Self test cycle/Startup behavior
When power is first applied, the sensor enters an
initial 60 second self-test cycle. During this time the
device does not respond to movement and stays on.
7. Range
9.8ft/3m
19.7ft/6m
29.5ft/9m
2
1
3
8 ft/
2.5 m
1
2
3
Walking across
Walking towards
Smaller movements
8. Exclude sources of interference
To prevent false activation from external heat-emitting
sources, use blinds to mask sensor viewing angle.
9. Description / Part No. / Accessory
Description
Part No.
FLAT-P-PP-A-FC
97032
FLAT-S-PP-FC
97033
Remote control:
via B.E.G. Controls IR-Adapter
92726
Power pack PP-A-J
97020
Power pack PP-1-J
97036
The required app for smartphones can be down-
loaded from the App Store for iOS smartphones and
Google Play Store for Android smartphones.
The manual for the B.E.G. Controls App can be
downloaded from www.begcontrols.com
Note:
Remote only works with primary FLAT-P-PP-A-
FC sensor.
Note:
Maximum distance between sensor and
remote - 24 ft / 7.3 m
10. Technical data
Operating voltage:
24 V DC
Ambient temperature:
-13°F-122°F/-25°C to +50°C
Protection:
Suitable for indoor use and dry locations
only.
Factory settings:
50 fc/500 Lux, 10 min.
Note:
Natural daylight contribution must be 2.5
times the artificial light contribution at the sensor for
the controlled load to turn-off.
Recommended height
for mounting:
8 - 10 ft / 2.4 - 3.0 m
Range of coverage Ø H 8 ft/2.50 m :
walking across 29.5 ft /9 m
walking towards 19.7 ft /6 m
smaller movements 9.8 ft /3 m
Area of coverage:
360°
Following settings can only be changed using the
B.E.G. Controls IR-Adapter for smartphones and app.
Switch-on threshold:
2 - 100 fc/20 - 1000 Lux
Follow-up time:
Load: 30 sec. - 30 min.
HVAC: 5 min. - 120 min.
Sensitivity:
MIN-LOW-MID-HIGH-MAX
Dimensions:
Ø 2.05 in H 1.9 in
Ø 52 x H 48 mm
Technical data FLAT-Secondary
Operating voltage:
24 V DC
Pulse output:
Digital output
11. Manual switching
!
See manual of the power pack PP-A/PP-1: “PB
load” and “All off” (only PP-A)!
12. LED-functional indicators
LED function indicators
Process
Red blinks once per
second during the
first 60 seconds after
powering
Self-test cycle, unmodified
device
Red blinks twice per
second during the
first 60 seconds after
powering
Self-test cycle, previously
modified device
Red flashes
Motion detected
Green blinks once per
second
Too bright detected
Red and green
flash once in quick
succession
Remote control signal
received
Red and green blink
together once every 4
seconds
Device operates in pulse
mode
Green is on for 4
seconds
Remote control signal
received but device is
locked
Green flashes twice per
second for 5 seconds
Device has just been
locked and can now be
double locked
44 mm
1.73 in