Self test cycle
After an initial 60-second self-test cycle, the
LUXOMAT
®
PD9-M-1C-FC is ready for operation.
(see
LED function displays see point 19).
Installation and Operating Instruction for
B.E.G.
- Mini occupancy detector PD9-M-1C(-GH)-FC
LUXOMAT
®
PD9-M-1C(-GH)-FC
1. Mounting preparation
Work on the mains supply may only
be carried out by qualified profes-
sionals or by instructed persons
under the direction and supervision
of qualified skilled electrical person-
nel in accordance with electrical
regulations.
Disconnect supply before installing!
When in Master/Slave mode of
operation, the Master-appliance
must always be installed at the
location where there is least
daylight.
5. Option: Remote control IR-PD-1C
Wall bracket for remote control
IR-PD-1C
GB
The detector has been
designed and developed
specifically for installation
in suspended ceilings.
A circular opening of
diameter min. 28 mm
must be produced in the
ceiling.
Having connected the cables in accordance with
the regulations, connect the power supply via the
RJ11 plug. Therefore, open the power supply with
the help of the screws and close it afterwards.
After that, put the power supply through the open-
ing in the ceiling and mount the sensor onto the
ceiling according to figure.
LED 1 green
LED 2 red
LED 3 white
2. Installation LUXOMAT
®
PD9-M-1C-FC
3. Hardware configuration
Position LED’s s
4. Putting into operation of the remote
control IR-PD-1C (optional)
Check Battery:
Open battery compartment
by pressing the plastic springs
together and removing the
battery-holder.
Caution:
Settings with remote control supersede the
settings by potentiometers.
LUXOMAT
®
PD3
B.E.G.
500
200
400
100
20
IR-PD-1C
PIR
CdS
ON/OFF
HA
B.E.G.
LUXOMAT
®
B.E.G.
LUXOMAT
®
7. Settings by remote control
An adhesive film for the surface of the IR-PD-1C is
included with the device. If required, this can be used
for any
B.E.G.
remote control with 27 keys.
8. Key functions in closed state
Light ON/OFF during the detection of
motion plus follow-up time; Activation
of the 12 h-ON/OFF-function by
holding down the push button
Switches channel off and is immedi-
ately active again, exits all timers,
interruption of light measurement
Permanent protection against sabotage
This function blocks the unit perma-
nently. This operating mode can only be
activated during the period of 5 seconds
(white LED flash) after pressing the “Lock“
button. The procedure for leaving this
mode is as follows:
1. Switch off the current
2. Apply current for 31 - 59 seconds
3.
Switch of the current again
4. Apply current, wait for selftest
cycle
5.
Open detector
Changes to „open“ state
Activation/Deactivation of the test
function
Confirmation
max
50
Lux
1500
Lux
ON
OFF
≥
28mm
1 2 3
The device distinguishes between 2 procedures:
•
Reading in with lighting switched on:
The switch-on value is determined automatically.
Determining the switch-on value:
1. Press the “eye“ push button
2. Switch off the light (2 seconds later)
3. Read in the brightness
4. Switch-on value = Read brightness
•
Reading in with lighting switched off:
When the push button is pressed, the current
brightness is specified as the switch-on value. The
switch-off value is determined automatically.
If the brightness has been modified, the switch-off
threshold is recalculated.
Each time the push button is pressed, the device
increases the current switch-on value in increments of
20 lux for a current switch-on value of < 100 lux and
in increments of 50 lux for a current switch-on value
of > 100 lux.
Standard sensitivity for most applications
Reduced sensitivity for outdoor applications
1000
20
+
9. Explanation of the remote control button functions
9 a. In the initialisation period
12 h Light ON/OFF (party function)
Activated by “Light“ - push button
Deactivated by “Reset“- push button (default)
Corridor function (see point 11 a)
Activated by “outside“- push button
Deactivate by “inside“- push button (default)
Forced shutdown (see point 11 c)
Activated by “sun“ - push button
Deactivate by “moon“- push button (default)
9 b. In opened state
This push button opens the detector and the following
functions can then be programmed.
Attention:
The detector is closed automatically:
• after every voltage recovery
• after 3 minutes
The state changes to “closed“.
In the first 5 seconds, the white LED flashes every 0.5
seconds. During this time, sabotage protection can be
activated.
When the pulse function is active, a pulse of 1 sec. is gener-
ated every 9 sec. If the pulse function is activated via remote
control, the pause between 2 pulses can be modified. After
activating the function via the “Pulse“ push button, select the
desired time within 5 sec.:
��
���
5
min
= 9 sec.,
��
���
10
min
= 10 sec.,
��
���
15
min
= 15 sec.,
��
���
30
min
= 30 sec.
The “Test“ push button can be used to set the LED ON/
OFF function. To do this, hold down the push button for
3 sec.
Please note
that in the open state and in test mode, the
LED indicators are always ON.
Twilight switch function (CdS)
If the CdS function is active, the detector acts as a simple
twilight switch. Only the brightness can be set in this mode.
Movements are no longer indicated by the red LED.
Push button acknowledgement:
Each push of a button is indicated by lamp acknowledgement
and by the white LED.
“Light ON“ status: OFF/ON (approx. 0.5 sec. each)
“Light OFF“ status: ON/OFF (approx. 0.5 sec. each)
PI R
CdS
S
R
L'
N
L
1-10 VDC
6.
Connections (at power supply)
t < 5 sec.
Unlocking device – Activation
of the programming mode
Locking device – Exit programming
mode
Change between fully automatic
and semi automatic mode (HA)
Luminance set point for channel 1
20 - 1000 Lux
Automatic reading in the current light
value as new luminance set point
Change between motion detector
and photo electric switch
Increase the current light level by
20 resp 50 Lux
Light ON/OFF
HA
ON/OFF
Resetting when
open:
Deletes all values
set with the re-
mote control, light
OFF.
or
1000
20
to
+
Follow-up time channel 1 (light)
5 - 30 min. or impuls
��
���
��
���
to
LED ON/OFF (by holding
down the push button)
or
Detection sensitivity reduced
or normal
��
���
5
min
Daytime operation, detector only
activated by motion
or
PI R
CdS
Permanent protection against
sabotage
white LED flashes
w
hen c
hoo
sing CdS
optional
optional
optional
optional
optional
optional
t < 5 sec.