PD4-M-HCL 93006/93007
50570_V1_Operation_Manual_PD4-M-
HCL_93006_93007_EN_080818
Page 6 / 10
Status LEDs
The status LEDs indicate
–
for example -
movement. PLEASE NOTE: In opened state
and in test mode the status LEDs are ACTIVE.
INI light
The INI-ON / INI-OFF function defines if the
light is on (INI-ON) or off (INI-OFF) during
self-test cycle (60s after mains supply).
Factory setting is INI-ON.
Start Burn In Function
Before the lamp can be dimmed, the
dimming function has to be suppressed for a
certain time in order to burn in the lamps.
T5 fluorescent lamps: 80 h
T8 fluorescent lamps: 100 h
During this time, the detector only switches
the light ON or OFF. A dimming to the set
value does not take place.
5.3. Human Centric Lighting
HCL Mode
Human
Centric
Lighting
(HCL)
can
synchronise the internal clock in rooms with
low daylight supply and sustainably
strengthen the well-being. By changing the
brightness and the light temperature during
the day, the dynamics of daylight are
brought into the building. This is done by
application profiles or via an external light
sensor. A demonstration mode is available
for testing purposes.
Application profiles
•
The "office" profile provides motivating
light. During the day, the brightness
ranges between approx. 500 and 650 lux
and the colour temperature between
approx. 3500 and 5500 Kelvin.
•
The
"Industry"
profile
provides
concentration-increasing light. During
the day, the brightness ranges between
approx. 500 and 750 lux and the colour
temperature between approx. 3500 and
5500 Kelvin.
•
The "School" profile offers motivating
light that supports learning. During the
day, the brightness ranges between
approx. 350 and 500 lux and the colour
temperature between approx. 3500 and
5500 Kelvin.
Date
Current date in the device. The current date
from the mobile is used when sending this
parameter.
Time
Current time in the device. The current time
from the mobile is used when sending this
parameter.
5.4. Lighting
Follow-up Time
This time period starts upon detected
movement and defines the duration for the
connected load to stay on.
Brightness set value
The brightness set value is the luminance
value to which the brightness in the room is
regulated. To define the set value, the
desired brightness can be adjusted using the
BRIGHTER/DARKER button and can be
stored with the EYE button. Fine tuning can
be achieved using the +/
–
buttons. The value
is stored automatically.
5.5. DALI groups 1-3: lighting zone A
Automatic
The operation mode of the detector can be
selected. FULL: In this operating mode, the
lighting switches automatically on and off
for increased comfort, depending on
presence and brightness. SEMI: In this
operating mode, the light turns on only after
a manual switching, for an increased savings
success. Switching off is automatically or
manually.In case motion is detected within
the 10sec. after elapse of the follow-up time,
the detector switches the light on again and
the follow-up time starts again. If there is no
motion detected within the 10s after elapse
of the follow-up time, the light has to be
turned on manually.
Offset group 2
Damping of group 2 relative to group 1 in %
Offset group 3
Damping of group 3 relative to group 1 in %