SmartSwarm 300 Series
:
61
Location
location
User-defined text e.g. Warehouse/Room401
Manufacturer
manufacturer
User-defined text (Usually the manufacturer of the slave)
Name
name
User-defined text e.g. AHU Fan
Product Code
product_code
User-defined text e.g. Wil-Flex-450
Byte Order
value_byte_order
This is how Floating Point and 32-bit data is ordered when
it is transmitted by the slave within the register.
No Swap
Swap Bytes and Words
Swap Bytes only
Swap Words only
Version
version
User-defined text e.g. 4.1
Table 19. Meta Data tab
An MQTT Topic hierarchy can be specified by using the ‘/’ character inline in the text of the meta data
fields. This hierarchy is not limited to 3 levels of <Location>/<Description>/<Name>
E.g. the text “Warehouse/HoldingArea/Room401” can be entered into the Location field.
Click on a cell to enter edit-mode. Use the tab key to navigate between cells. If the data entered is
invalid, the cell color will change to red. Pressing the ESC key while in edit-mode will restore the original
value.
Changes are automatically saved when moving to a new tab.
9.4.3 REGISTERS
The application supports the 4 Modicon register types i.e. Coils, Discrete Inputs, Input Registers and Holding
Registers.
Register Type
Address Range
Modicon Address
Coil (0x)
0-65535
000001 to 065536
Discrete Input (1x)
0-65535
100001 to 165536
Input Registers (3x)
0-65535
300001 to 365536
Holding Registers (4x)
0-65535
400001 to 465536
Table 20. Register Types